Bulletin 284e – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 247
![background image](/manuals/578181/247/background.png)
Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
247
Specifications for EtherNet/IP Chapter 11
Bulletin 284E
Electrical Ratings
UL/NEMA
IEC
Power Circuit
Rated Operation Voltage
200…575V
200…500V
Rate Insulation Voltage
600V
600 V
Rated Impulsed Voltage
6 kV
6 kV
Dielectric Withstand
2200V AC
2500V AC
Operating Frequency
50/60 Hz
50/60 Hz
Utilization Category
N/A
AC-3
Protection Against Shock
N/A
IP2X
Control
Circuit
Rated Operation Voltage
24V DC (+10%, –15%) A2 (should be grounded at voltage source)
Rate Insulation Voltage
250V
250V
Rated Impulsed Voltage
—
4 kV
Dielectric Withstand
1500V AC
2000V AC
Overvoltage Category
—
III
Operating Frequency
50/60 Hz
50/60 Hz
Short Circuit
Protection
SCPD Performance Type 1
Current Rating
Voltage
480Y/277V
480Y/480V
600Y/347V
600V
10 A
Sym. Amps rms
65 kA
65 kA
30 kA
30 kA
25 A
30 kA
30 kA
30 kA
30 kA
SCPD List
Size per NFPA 70 (NEC) or NFPA 79 for Group Motor Applications
UL/NEMA
IEC
Environmental
Operating Temperature Range
–20…40°C (–4…104°F)
Storage and Transportation
Temperature Range
–25….85°C (–13…185°F)
Altitude
1000 m
Humidity
5…95% (on-condensing)
Pollution Degree
3
Enclosure Ratings
NEMA 4/12
IP67
Approximate Shipping Weight
13.6 kg (30 lb)
Mechanical
Resistance to Shock
Operational 15
G
Non-Operational 30
G
Resistance to Vibration
Operational
1 G, 0.15 mm (0.006 in.) Displacement
Non-Operational
2.5 G, 0.38 mm (0.015 in.) Displacement
Power and Ground Terminals
Wire Size
Primary/Secondary Terminal:
#16…#10 AWG
Primary/Secondary Terminal:
1.0…4.0 mm2
Tightening Torque
Primary Terminal: 10.8 lb·in.
Secondary Terminal: 4.5 lb·in.
Primary Terminal: 1.2 N·m
Secondary Terminal: 0.5 N·m
Wire Strip Length
0.35 in. (9 mm)
Control and Safety Monitor Inputs
WireSize
#18…#10 AWG
1.0…4.0 mm2
Tightening Torque
6.2 lb·in.
0.7 N·m
Wire Strip Length
0.35 in. (9 mm)
Disconnect Lock Out
Maximum of 5/16 in. (8 mm) lock shackle or hasp. The hasp should not exceed
5/16 in. (8 mm) when closed, or damage will occur to disconnect guard.