Chapter 5 Using the I/O

recommended using the RSLogix 5000 device Add-on Profiles to take advantage
of their benefits (more intuitive, time saving, and less likely to make ladder logic
program errors).

Creating Ladder Logic Using the RSLogix 5000 Generic Profile, All

Versions

Drive and Adapter Parameter Settings

The following drive and adapter settings were used for the example ladder logic
program in this section.

Device

Parameter

Value

Description

PowerFlex 70 EC

Drive

90 - [Speed Ref A Sel]

22 (DPI Port 5)

Assigns 20-COMM-ER to be used for the Reference.

300 - [Data In A1]

140

Points to Par. 140 - [Accel Time 1]

301 - [Data In A2]

142

Points to Par. 142 - [Decel Time 1]

302 - [Data In B1]

100

Points to Par. 100 - [Jog Speed]

303 - [Data In B2]

155

Points to Par. 155 - [Stop Mode A]

304 - [Data In C1]

101

Points to Par. 101 - [Preset Speed 1]

305 - [Data In C2]

102

Points to Par. 102 - [Preset Speed 2]

306 - [Data In D1]

103

Points to Par. 103 - [Preset Speed 3]

307 - [Data In D2]

104

Points to Par. 104 - [Preset Speed 4]

310 - [Data Out A1]

140

Points to Par. 140 - [Accel Time 1]

311 - [Data Out A2]

142

Points to Par. 142 - [Decel Time 1]

312 - [Data Out B1]

100

Points to Par. 100 - [Jog Speed]

313 - [Data Out B2]

155

Points to Par. 155 - [Stop Mode A]

314 - [Data Out C1]

101

Points to Par. 101 - [Preset Speed 1]

315 - [Data Out C2]

102

Points to Par. 102 - [Preset Speed 2]

316 - [Data Out D1]

103

Points to Par. 103 - [Preset Speed 3]

317 - [Data Out D2]

104

Points to Par. 104 - [Preset Speed 4]

20-COMM-ER

Adapter

04 - [IP Addr Cfg 1]

07 - [IP Addr Cfg 4]

10.91.100.79

IP address for the adapter.

08 - [Subnet Cfg 1]

11 - [Subnet Cfg 4]

255.255.248.0

Subnet mask for the adapter.

23 - [DPI I/O Cfg]

xxx1 1111

Enables Cmd/Ref and Datalinks A…D.

35 - [M-S Input]

xxx1 1111

Configures the I/O Data to be transferred from the controller on

the network to the drive.

36 - [M-S Output]

xxx1 1111

Configures the I/O Data to be transferred from the drive to the

controller on the network.

TIP

Data In parameters are inputs into the device that come from controller

outputs (for example, data to write to a device parameter). Data Out

parameters are outputs from the device that go to controller inputs (for
example, data to read a device parameter).