Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

171

Appendix

B

Adapter Parameters

This appendix provides information about the adapter parameters.

About Parameter Numbers

The parameters in the adapter are numbered consecutively. However, depending
on which configuration tool you use, they may have different numbers.

Parameter List

Topic

Page

About Parameter Numbers

171

Parameter List

171

Configuration Tool

Numbering Scheme

HIM

Connected Components Workbench software

DriveExplorer

DriveExecutive

The adapter parameters begin with parameter

01. For example, Parameter 01 - [DPI Port] is

parameter 01 as indicated by this manual.

Explicit Messaging

See

Chapter 6

,

Using Explicit Messaging

and

Appendix C

,

EtherNet/IP Objects

for details.

Parameter
No. Name and Description

Details

01

[DPI Port]
Displays the port to which the adapter is

connected. This will usually be port 5.

Default:

5

Minimum:

0

Maximum:

7

Type:

Read Only

02

[DPI Data Rate]
Displays the data rate used by the drive. This data

rate is set in the drive and the adapter detects it.

Default:

0 = 125 kbps

Values:

0 = 125 kbps

1 = 500 kbps

Type:

Read Only

03

[BOOTP/DHCP]
Configures the adapter to use BOOTP so that you

can set its IP address, subnet mask, and gateway

address with a BOOTP server.

Default:

1 = Enabled

Values:

0 = Disabled

1 = Enabled

Type:

Read/Write

Reset Required: Yes