Appendix B Adapter Parameters
44
45
46
47
[Peer Inp Addr 1]
[Peer Inp Addr 2]
[Peer Inp Addr 3]
[Peer Inp Addr 4]
Sets the IP address bytes that specifies the device
from which the adapter receives (consumes) peer
I/O data.
Important: The Peer Inp Addr must be on the
same subnet as the 20-COMM-ER. See
for more information.
Changes to these parameters are ignored when
Parameter 49 - [Peer Inp Enable] is set to ‘1’
(On).
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
255
Type:
Read/Write
Reset Required: No
48
[Peer Inp Timeout]
Sets the timeout for a peer I/O connection. If the
time is reached without the adapter receiving
(consuming) a message, the adapter will respond
with the action specified in Parameter 43 - [Peer
Flt Action].
In an adapter receiving (consuming) peer I/O, the
value of this parameter must be greater than the
product of the value of Parameter 54 - [Peer Out
Time] in the adapter transmitting (producing) peer
I/O multiplied by the value of Parameter 55 - [Peer
Out Skip] in the adapter transmitting (producing)
peer I/O.
Default:
10.00 Seconds
Minimum:
0.01 Seconds
Maximum:
10.00 Seconds
Type:
Read/Write
Reset Required: No
49
[Peer Inp Enable]
Determines if peer I/O input is on or off.
Default:
0 = Off
Values:
0 = Off
1 = On
Type:
Read/Write
Reset Required: No
50
[Peer Inp Status]
Displays the status of the consumed peer I/O input
connection.
Default:
0 = Off
Values:
0 = Off
1 = Waiting
2 = Running
3 = Faulted
Type:
Read Only
Parameter
No. Name and Description
Details
255 . 255 . 255 . 255
[Peer Inp Addr 1]
[Peer Inp Addr 2]
[Peer Inp Addr 3]
[Peer Inp Addr 4]