Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual
Page 25

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
25
Installing the Adapter Chapter 2
Table 1 - Drive and Adapter Start-Up Status Indications
After verifying correct operation, close or install the drive cover. For more details
on status indicator operation, see
.
Item Name
Color
State
Description
Drive STS Indicator
➊
STS (Status)
refer to drive
or SMC
manual for
status
indication
information)
Green
Flashing
Device ready but not running, and no faults are present.
Steady
Device running, no faults are present.
Yellow
Flashing,
device stopped
An inhibit condition exists – the drive cannot be started. Check device Parameter 214 - [Start
Inhibits].
Flashing,
device running
An intermittent type 1 alarm condition is occurring. Check device Parameter 211 - [Drive Alarm 1].
Steady,
device running
A continuous type 1 alarm condition exists. Check device Parameter 211 - [Drive Alarm 1].
Red
Flashing
A fault has occurred.
Steady
A non-resettable fault has occurred.
Adapter Status Indicators
➋
PS
Off
Steady
No power
Orange Flashing
Requesting DPI I/O Connections
Steady
Peripheral is Connected to an incompatible product or no DPI ping events are detected.
Green
Flashing
Normal Operation (DPI connected) - No I/O, or PLC in Program
Steady
Normal Operation (DPI connected) - I/O Operational
Red
Flashing
DPI Problem, Bad CRC of Adapter Parameters or Flash Program
Steady
DPI Failure or Failed power-on diagnostic test (hardware failure)
Green/
Red
Flashing
Flash update in progress
NS
Off
Steady
No power OR no IP Address
Green
Flashing
An IP address is configured, but no CIP connections are established, and an Exclusive Owner
connection has not timed out
Steady
At least one CIP connection (any transport class) is established, and an Exclusive Owner
connection has not timed out
Red
Flashing
Connection has timed out see the “The EtherNet Adaptation of CIP” Specification sections 9-4.4
for detailed behavior description
Steady
Duplicate IP Address detected
Orange Steady
Adapter Failure (used in conjunction with PS orange)
Green/
Red
Flashing
Self-test on power up
LS1
Off
Steady
No Network Activity
Green
Flashing
Network activity at 100 Mbps
Yellow
Flashing
Network activity at 10 Mbps
LS2
Off
Steady
No Network Activity
Green
Flashing
Network activity at 100 Mbps
Yellow
Flashing
Network activity at 10 Mbps