Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual
Page 117

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
117
Using Explicit Messaging Chapter 6
ControlLogix Controller – Formatting a Message to Write Multiple
Parameters, RSLogix 5000 Software, All Versions
Figure 44 - Scattered Write Multiple Message Configuration Screens
The following table identifies the data that is required in each box to configure a
message to write multiple parameters.
Configuration Tab
Example Value
Description
Message Type
Service Type
(1)
Service Code
Class
Instance
Attribute
Source Element
Source Length
Destination
CIP Generic
Custom
4c (Hex.)
93 or 9F (Hex.)
(3)
0 (Dec.)
0 (Hex.)
Scattered_Write_Request
(4)
Scattered_Write_Response
Used to access Parameter Object in the adapter.
Required for scattered messages.
Code for the requested service.
Class ID for the DPI Parameter Object.
Required for scattered messages.
Required for scattered messages.
Name of the tag for any service data to be sent from scanner or bridge to the adapter/drive.
Number of bytes of service data to be sent in the message.
The tag where the data that is read is stored.
Communication Tab Example Value
Description
Path
(2)
My_PowerFlex_Drive
The path is the route that the message will follow.
Tag Tab
Example Value
Description
Name
Scattered_Write_Message
The name for the message.
(1) The default setting for Service Type is ‘Custom’, enabling entry of a Service Code not available from the Service Type pull-down menu. When choosing a Service Type
other than ‘Custom’ from the pull-down menu, an appropriate Hex. value is automatically assigned to the Service Code box which is dimmed (unavailable).
(2) Click Browse to find the path, or type in the name of the device listed in the I/O Configuration folder.
(3) See
for limitations of PowerFlex 7-Class drives when using DPI Parameter Object Class code 0x93 for explicit messaging.
(4) In this example, we are writing to five parameters. Each parameter being written to requires an array of three INT registers. Therefore, a controller tag was created with
its Data Type field set to ‘INT[15]’. Also, the Source Length field on the Message Configuration screen must correspond to the selected Data Type in bytes (for this
example, 30 bytes for an INT[15] array). Scattered write messages always assume that every parameter being written to is a 32-bit parameter, regardless of its actual
size. Maximum length is 132 bytes or 66 words which equates to 22 parameters. For parameter numbering, see