Appendix C EtherNet/IP Objects
Instance Attributes
Important: Setting an assembly object attribute can be done only when the
Control Timeout (class attribute 100) has been set to a non-zero
value.
Register Object
Class Code
Services
Instances
Attribute ID
Access Rule
Name
Data Type
Description
1
Get
Number of
Members
WORD
1
2
Get
Member List
ARRAY of STRUCT:
WORD
WORD
Packed EPATH
Size of member data
Size of member path
Member path
3
Conditional
(1)
(1) For instance 1, access rule for the data attribute is Get. For instance 2, it is Get/Set.
Data
Array of Bits
Data to be transferred
4
Get
Size
WORD
Size of assembly data in bits
Hexadecimal
Decimal
0x07
7
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
Yes
Yes
Set_Attribute_Single
Instance
Description
1
All I/O data being read from the DPI device (read-only)
2
All I/O data written to the DPI device (read/write)
3
Logic Status and Feedback data (read-only)
4
Logic Command and Reference data (read/write)
5
Datalink A (input data from device to scanner) (read only)
6
Datalink A (output data from scanner to device) (read/write)
7
Datalink B (input data from device to scanner) (read only)
8
Datalink B (output data from scanner to device) (read/write)
9
Datalink C (input data from device to scanner) (read only)
10
Datalink C (output data from scanner to device) (read/write)
11
Datalink D (input data from device to scanner) (read only)
12
Datalink D (output data from scanner to device) (read/write)
13
Logic Status and Feedback Data (read-only)
14
Mask
(1)
(read/write)
(1) The mask command word is set to the value of the first word of the data where there are ones in the second word of the data.
Command = (word 1 and not word 2) or (word 1 and word 2). This only controls specified bits in the Logic Command data to the DPI
product and does not change the Reference value.
15
Logic Status (read-only)
16
Logic Command (read/write)
17
Feedback (read-only)
18
Reference (read/write)