beautypg.com

Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual

Page 174

background image

174

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

Appendix B Adapter Parameters

23

[Comm Flt Action]
Sets the action that the adapter and drive will take

if the adapter detects that I/O communication has

been disrupted. This setting is effective only if I/O

that controls the drive is transmitted through the

adapter. When communication is re-established,

the drive will automatically receive commands over

the network again.

Default:

0 = Fault

Values:

0 = Fault

1 = Stop

2 = Zero Data

3 = Hold Last

4 = Send Flt Cfg

Type:

Read/Write

Reset Required: No

24

[Idle Flt Action]
Sets the action that the adapter and drive will take

if the adapter detects that the controller is in

program mode or faulted. This setting is effective

only if I/O that controls the drive is transmitted

through the adapter. When the controller is put

back in Run mode, the drive will automatically

receive commands over the network again.

Default:

0 = Fault

Values:

0 = Fault

1 = Stop

2 = Zero Data

3 = Hold Last

4 = Send Flt Cfg

Type:

Read/Write

Reset Required: No

25

[DPI I/O Cfg]
Sets the I/O that is transferred through the adapter.

Default:

xxx0 0001

Bit Values:

0 = I/O Disabled

1 = I/O Enabled

Type:

Read/Write

Reset Required: Yes

Parameter
No. Name and Description

Details

ATTENTION: Risk of injury or equipment damage exists. Parameter 23 -

[Comm Flt Action] lets you determine the action of the adapter and connected

drive if I/O communication is disrupted. By default, this parameter faults the

drive. You can set this parameter so that the drive continues to run, however,

precautions should be taken to verify that the setting of this parameter does not

create a risk of injury or equipment damage. When commissioning the drive,

verify that your system responds correctly to various situations (for example, a

disconnected cable).

ATTENTION: Risk of injury or equipment damage exists. Parameter 24 - [Idle

Flt Action] lets you determine the action of the adapter and connected drive

when the controller is idle. By default, this parameter faults the drive. You can

set this parameter so that the drive continues to run, however, precautions

should be taken to verify that the setting of this parameter does not create a risk

of injury or equipment damage. When commissioning the drive, verify that your

system responds correctly to various situations (for example, a faulted

controller).

Bit

Definition

Not

Used

Not

Used

Not

Used

Dat

alink

D

Dat

alink

C

Dat

alink

B

Dat

alink

A

Cm

d/Ref

Default

x

x

x

0 0 0 0 1

Bit

7 6 5 4 3 2 1 0