A160, A163, Advanced program group (continued) – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 98

3-40
Programming and Parameters
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Advanced Program Group (continued)
A160 [Process Factor]
Related Parameter(s):
Scales the output frequency value displayed by
[Process Display].
Values
Default:
30.0
Min/Max:
0.1/999.9
Display:
0.1
Output Freq
Process Factor
Process Display
=
x
A163 [Auto Rstrt Tries]
Related Parameter(s):
,
,
Sets the maximum number of times the drive attempts to reset a fault and restart.
Clear a Type 1 fault and restart the drive.
1. Set A163 [Auto Rstrt Tries] to a value other than “0”.
2. Set
[Auto Rstrt Delay] to a value other than “0”.
Clear an OverVoltage, UnderVoltage or Heatsink OvrTmp fault without restarting the drive.
1. Set A163 [Auto Rstrt Tries] to a value other than “0”.
2. Set
[Auto Rstrt Delay] to “0”.
Note: If the parameter is not set to zero and [Auto Rstrt Time] is set to zero, auto fault clear is enabled.
This feature automatically clears faults, but does not restart the drive.
Values
Default:
0
Min/Max:
0/9
Display:
1
ATTENTION:
Equipment damage and/or personal injury may result if this parameter
is used in an inappropriate application. Do not use this function without considering
applicable local, national and international codes, standards, regulations or industry
guidelines.
A164 [Auto Rstrt Delay]
Related Parameter(s):
Sets the time between restart attempts when
[Auto Rstrt Tries] is set to a value other than zero.
Note: If the parameter is not set to zero and [Auto Rstrt Time] is set to zero, auto fault clear is enabled.
This feature automatically clears faults, but does not restart the drive.
Values
Default:
1.0 Secs
Min/Max:
0.0/160.0 Secs
Display:
0.1 Secs