Advanced display group, Advanced display group -60, D302 – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 118: D301, D301 [control source, D302 [contrl in status

3-60
Programming and Parameters
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Advanced Display Group
d301 [Control Source]
Related Parameter(s):
,
Displays the active source of the Start Command and Speed Command which are normally defined
by the settings of
[Start Source] and
[Speed Reference] but may be overridden by digital
inputs. Refer to the flowcharts on pages
and
for details.
Values
Default:
Read Only
Min/Max:
0/99
Display:
1
Start Command
Digit 0
0 = Keypad
1 = Terminal Block
2 = Communications
Speed Command
Digit 1
0 = Local Keypad Potentiometer
1 =
[Internal Freq]
2 = Analog Input 1
3 = Analog Input 2
4 =
[Preset Freq x]
(
[Digital Inx Sel] must be set to 4)
5 = Communications
Reserved
Digit 2
Reserved
Digit 3
d302 [Contrl In Status]
Related Parameter(s):
,
Status of the control terminal block control inputs.
Important: Actual control commands may come from a source other than the control terminal block.
Values
Default:
Read Only
Min/Max:
0/1
Display:
1
1 = Condition True, 0 = Condition False
Start/FWD In
I/O Terminal 02
Dir/REV In
I/O Terminal 03
Stop Input
I/O Terminal 01
Digital In 1
I/O Terminal 05
Digital In 2
I/O Terminal 06
Digital In 3
I/O Terminal 07
Digital In 4
I/O Terminal 08
Not Used