Advanced program group (continued), A206 [act1 minimum, A207 [act1 maximum – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 111: A208 [act2 minimum, A209 [act2 maximum

Programming and Parameters
3-53
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Advanced Program Group (continued)
A206 [ACT1 Minimum]
Related Parameter(s):
(with FRN 7.xx and later.)
Sets the minimum value of the actual (ACT) 1 input. Used with the analog input min/max settings to
scale the analog input for use as the PID feedback. Can be used in a normal and inverted mode.
Values
Default:
0.0%
Min/Max:
0.0/200.0%
Display:
0.1%
A207 [ACT1 Maximum]
ACT1 %
Normal
A206 [ACT1 Minimum]
T070 [Analog In 1 Lo]
T071 [Analog In 1 Hi]
A206 [ACT1 Minimum]
ACT1 %
Inverted
A207 [ACT1 Maximum]
T070 [Analog In 1 Lo]
T071 [Analog In 1 Hi]
A207 [ACT1 Maximum]
Related Parameter(s):
(with FRN 7.xx and later.)
Sets the maximum value of the actual (ACT) 1 input.
Values
Default:
100.0%
Min/Max:
0.0/200.0%
Display:
0.1%
A208 [ACT2 Minimum]
Related Parameter(s):
(with FRN 7.xx and later.)
Sets the minimum value of the actual (ACT) 2 input. Used with the analog input min/max settings to
scale the analog input for use as the PID feedback. Can be used in a normal and inverted mode.
Values
Default:
0.0%
Min/Max:
0.0/200.0%
Display:
0.1%
A209 [ACT2 Maximum]
ACT2 %
Normal
A208 [ACT2 Minimum]
T074 [Analog In 2 Lo]
T075 [Analog In 2 Hi]
A208 [ACT2 Minimum]
ACT2 %
Inverted
A209 [ACT2 Maximum]
T074 [Analog In 2 Lo]
T075 [Analog In 2 Hi]
A209 [ACT2 Maximum]
Related Parameter(s):
(with FRN 7.xx and later.)
Sets the maximum value of the actual (ACT) 2 input.
Values
Default:
100.0%
Min/Max:
0.0/200.0%
Display:
0.1%