Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 186

D-10
Application Notes
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Guidelines for Adjusting the PID Gains
1. Adjust the proportional gain. During this step it may be desirable to
disable the integral gain and differential gain by setting them to 0.
After a step change in the PID Feedback:
–
If the response is too slow increase
[PID Prop Gain].
–
If the response is too quick and/or unstable (see
[PID Prop Gain].
–
[PID Prop Gain] is set to some value below the
point where the PID begins to go unstable.
2. Adjust the integral gain (leave the proportional gain set as in Step 1).
After a step change in the PID Feedback:
–
If the response is too slow (see
), or the PID Feedback
does not become equal to the PID Reference, decrease
[PID Integ Time].
–
If there is a lot of oscillation in the PID Feedback before settling
out (see
[PID Integ Time].
3. At this point, the differential gain may not be needed. However, if
after determining the values for
[PID Prop Gain] and
[PID Integ Time]:
–
Response is still slow after a step change, increase
[PID
Diff Rate].
–
Response is still unstable, decrease
[PID Diff Rate].