Network Points
Table G.1 Point Database for Application 2735
Point
Number
Point
Type
Subpoint Name
Factory
Default
(SI Units)
Engineering
Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
01
LAO
CTLR ADDRESS
99
–
1
0
–
–
02
LAO
APPLICATION
2735
–
1
0
–
–
{03}
LAI
FREQ OUTPUT
0
HZ
0.01
0
–
–
{04}
LAI
PCT OUTPUT
0
PCT
0.1
0
–
–
{05}
LAI
SPEED
0
RPM
1
0
–
–
{06}
LAI
CURRENT
0
AMPS
0.1
0
–
–
{07}
LAI
TORQUE
0
AMPS
0.1
0
–
–
{08}
LAI
POWER
0
HP
(KW)
0.1333
(0.1)
0
(0)
–
–
{09}
LAI
DRIVE TEMP
0
DEG F
(DEG C)
1.8
(1)
32
(0)
–
–
{11}
LAI
DRIVE MWH
0
MWH
0.1
0
–
–
{12}
LAI
RUN TIME
0
HRS
10
0
–
–
{13}
LAI
DC BUS VOLT
0
VOLTS
1
0
–
–
20
LAO
OVRD TIME
1
HRS
1
0
–
–
{21}
LDI
FWD.REV MON
FWD
–
1
0
REV
FWD
{22}
LDO
CMD FWD.REV
FWD
–
1
0
REV
FWD
{23}
LDI
RUN.STOP MON
STOP
–
1
0
RUN
STOP
{24}
LDO
CMD RUN.STOP
STOP
–
1
0
RUN
STOP
{25}
LDI
READY
READY
–
1
0
READY
NOTRDY
{26}
LDO
RUN ENABLE
STOP
–
1
0
ENABLE
STOP
{29}
LDO
DAY NGT
DAY
–
1
0
NIGHT
DAY
30
LAO
CURRENT LIMT
*1
AMPS
0.1
0
–
–
31
LAO
ACCEL TIME
20
SEC
0.02
0
–
–
32
LAO
DECEL TIME
20
SEC
0.02
0
–
–
33
LDO
KEYPAD LOCK
UNLOCK
–
1
0
LOCK
UNLOCK
{36}
LAO
READ PARAM
0
–
1
0
–
–
{37}
LAI
READ VALUE
0
–
1
0
–
–
{38}
LAO
WRITE PARAM
0
–
1
0
–
–
{39}
LAO
WRITE VALUE
0
–
1
0
–
–
{40}
LDO
DIGITAL OUT1
OFF
–
1
0
ON
OFF
{41}
LDO
DIGITAL OUT2
OFF
–
1
0
ON
OFF
{42}
LDO
DIGITAL OUT3
OFF
–
1
0
ON
OFF
{43}
LDO
OPT RELAY 1
OFF
–
1
0
ON
OFF
{44}
LDO
OPT RELAY 2
OFF
–
1
0
ON
OFF
{45}
LDO
OPT RELAY 3
OFF
–
1
0
ON
OFF
{46}
LDO
OPT RELAY 4
OFF
–
1
0
ON
OFF
{47}
LDO
OPT RELAY 5
OFF
–
1
0
ON
OFF
{48}
LDO
OPT RELAY 6
OFF
–
1
0
ON
OFF
{49}
LDI
DIGITAL IN 1
OFF
–
1
0
ON
OFF
{50}
LDI
DIGITAL IN 2
OFF
–
1
0
ON
OFF
{51}
LDI
DIGITAL IN 3
OFF
–
1
0
ON
OFF
{52}
LDI
DIGITAL IN 4
OFF
–
1
0
ON
OFF
{53}
LDI
DIGITAL IN 5
OFF
–
1
0
ON
OFF
{54}
LDI
DIGITAL IN 6
OFF
–
1
0
ON
OFF
{55}
LDI
DIGITAL IN 7
OFF
–
1
0
ON
OFF
{60}
LAI
INPUT REF 1
0
*3
0.1
0
–
–
{61}
LAI
INPUT REF 2
0
*3
0.1
0
–
–
{62}
LAO
ANALOG OUT 1
0
PCT
0.1
0
–
–
{63}
LAO
ANALOG OUT 2
0
PCT
0.1
0
–
–
{64}
LAI
LAST FAULT
0
–
1
0
–
–