T065, Terminal block group, Continued) – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 76

3-18
Programming and Parameters
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Terminal Block Group
(continued)
T065 [Opto Out Sel]
Related Parameter(s):
,
Determines the operation of the programmable opto output.
Options
0 “Ready/Fault”
Opto output is active when power is applied. This indicates
that the drive is ready for operation. Opto output is inactive
when power is removed or a fault occurs.
1 “At Frequency”
(Default)
Drive reaches commanded frequency.
2 “MotorRunning”
Motor is receiving power from the drive.
3 “Hand Active”
Active when drive is in local control.
4 “Motor Overld”
Motor overload condition exists.
5 “Ramp Reg”
Ramp regulator is modifying the programmed accel/decel
times to avoid an overcurrent or overvoltage fault from
occurring.
6 “Above Freq”
•
Drive exceeds the frequency (Hz) value set in
[Opto
Out Level].
•
Use T066 to set threshold.
7 “Above Cur”
•
Drive exceeds the current (% Amps) value set in
[Opto Out Level].
•
Use T066 to set threshold.
Important: Value for
[Opto Out Level] must be entered
in percent of drive rated output current.
8 “Above DCVolt”
•
Drive exceeds the DC bus voltage value set in
[Opto
Out Level].
•
Use T066 to set threshold.
9 “Above Anlg 2”
•
Analog input voltage (I/O Terminal 17) exceeds the value
set in
[Opto Out Level].
•
Do not use if
[Analog In 2 Sel] is set to 3 “Voltage
Mode - Bipolar”.
•
This parameter setting can also be used to indicate a PTC
trip point when the input (I/O Terminal 17) is wired to a
PTC and external resistor.
•
Use T066 to set threshold.
10 “Above PF Ang”
•
Power Factor angle has exceeded the value set in
[Opto Out Level].
•
Use T066 to set threshold.
11 “Anlg In Loss”
Analog input loss has occurred. Program
[Analog In 1
[Analog In 2 Loss] for desired action when
input loss occurs.
12 “ParamControl”
Enables the output to be controlled over network
communications by writing to
[Opto Out Level].
(0 = Off, 1 = On.)
13 “Retries Exst”
Value set in
[Auto Rstrt Tries] is exceeded.
14 “NonRec Fault”
•
Number of retries for
[Auto Rstrt Tries] is exceeded
OR
•
Non-resettable fault occurs OR
•
[Auto Rstrt Tries] is not enabled.
15 “Reverse”
Drive is commanded to run in reverse direction.