Page 109: Advanced program group (continued)

Programming and Parameters
3-51
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Advanced Program Group (continued)
A196 [Testpoint Sel]
Related Parameter(s):
Used by Rockwell Automation field service personnel.
Values
Default:
1024
Min/Max:
1024/65535
Display:
1
A197 [Fault Clear]
Related Parameter(s):
,
Stop drive before changing this parameter.
Resets a fault and clears the fault queue. Used primarily to clear a fault over network communications.
Options
0 “Ready/Idle” (Default)
1 “Reset Fault”
2 “Clear Buffer”
Clears all fault buffers.
A198 [Program Lock]
Protects parameters against change by unauthorized personnel. Enter a user-selected password to
lock the parameters via Option 1. Enter the same password to unlock the parameters.
Options
0 “Unlocked” (Default)
1 “Locked”
Locks all parameters.
2 “Locked”
Parameter edits allowed over communications network.
3 “Locked”
Locks
[Maximum Freq] and
[Boost Select].
A199 [Motor NP Poles]
Related Parameter(s):
Sets the motor poles. This is used to calculate
[Output RPM].
Values
Default:
4
Min/Max:
2/40
Display:
1
A200 [Motor NP FLA]
Related Parameter(s):
Set to the motor nameplate rated full load amps.
Values
Default:
Drive Rated Amps
Min/Max:
0.1/(Drive Rated Amps
×
2)
Display:
0.1 Amps