T069, T070, T071 – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 78: Terminal block group, Continued), T069 [analog in 1 sel, T070 [analog in 1 lo, T071 [analog in 1 hi

3-20
Programming and Parameters
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Terminal Block Group
(continued)
T069 [Analog In 1 Sel]
Sets the analog input signal mode (0-20mA, 4-20mA, or 0-10V). This parameter must match DIP
Switch AI1 setting on the control board.
Values
Default:
2
Min/Max:
0/6
Display:
1
T069 Option
Setting
Input Range
DIP Switch AI1 Setting
0
Current Mode
0-20 mA
20 mA
1
Current Mode
4-20 mA
20 mA
2
Voltage Mode - Unipolar
0-10V
10V
4
Current Mode (Square Root)
0-20 mA
20 mA
5
Current Mode (Square Root)
4-20 mA
20 mA
6
Voltage Mode - Unipolar (Square Root) 0-10V
10V
T070 [Analog In 1 Lo]
,
Stop drive before changing this parameter.
Sets the analog input level that corresponds to
[Minimum Freq].
Analog inversion can be accomplished by setting this value larger than T071 [Analog In 1 Hi].
Important: If analog inversion is implemented the drive will go to maximum frequency in the event the
analog input is lost. It is strongly recommended to activate T072 [Analog In 1 Loss] to protect from this
potential occurrence.
Values
Default:
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%
0
P035 [Maximum Freq]
P034 [Minimum Freq]
T070 [Analog In 1 Lo]
T071 [Analog In 1 Hi]
0
Speed Reference
T071 [Analog In 1 Hi]
,
Stop drive before changing this parameter.
Sets the analog input level that corresponds to P035 [Maximum Freq].
Analog inversion can be accomplished by setting this value smaller than T070 [Analog In 1 Lo].
Values
Default:
100.0%
Min/Max:
0.0/100.0%
Display:
0.1%