background image

Application Notes

D-7

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

Invert Function

For a 4-20mA signal, the following parameter settings are used so that a
20mA signal = 0% PID Reference and a 4mA signal = 100% PID
Reference.

T069

[Analog In 1 Sel] or

T073

[Analog In 2 Sel] = 1 “Current

Mode 4-20 mA”

T070

[Analog In 1 Lo] or

T074

[Analog In 2 Lo] = 100.0%

T071

[Analog In 1 Hi] or

T075

[Analog In 2 Hi] = 0.0%

A152

[PID Ref Sel] = 2 “Analog In 1” or 3 “Analog In 2”

PID Deadband

Parameter

A158

[PID Deadband] is used to set a range, in percent, of the

PID Reference that the drive will ignore.

Example

[PID Deadband] is set to 5.0

The PID Reference is 25.0%

The PID Regulator will not act on a PID Error that falls between 20.0
and 30.0%

0 10 20 30 40 50 60 70 80 90 100

PID Reference (%)

4-20mA Input

4

8

12

16

20

24