A186, A182, A183 – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 105: Advanced program group (continued)

Programming and Parameters
3-47
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Advanced Program Group (continued)
A182 [Drive OL Mode]
Related Parameter(s):
,
Determines how the drive handles overload conditions that would otherwise cause the drive to fault.
Options
0 “DIsabled”
1 “Reduce CLim”
2 “Reduce PWM”
3 “Both-PWM 1st” (Default)
A183 [SW Current Trip]
Related Parameter(s):
Enables/disables a software instantaneous (within 100 ms) current trip.
Values
Default:
0.0 (Disabled)
Min/Max:
0.0/(Drive Rated Amps
×
1.8)
Display:
0.1 Amps
A184 [Load Loss Level]
Related Parameter(s):
Provides a software trip (Load Loss fault) when the current drops below this level for the time specified
in [Load Loss Time].
Values
Default:
0.0 (Disabled)
Min/Max:
0.0/Drive Rated Amps
Display:
0.1 Amps
A185 [Load Loss Time]
Related Parameter(s):
Sets the required time for the current to be below [Load Loss Level] before a Load Loss fault occurs.
Values
Default:
0 Secs (Disabled)
Min/Max:
0/9999 Secs
Display:
1 Secs
A186 [Stall Fault Time]
Sets the time that the drive will remain in stall mode before a fault is issued.
Options
0 “60 Seconds” (Default)
1 “120 Seconds”
2 “240 Seconds”
3 “360 Seconds”
4 “480 Seconds”
5 “Flt Disabled”