Basic Program Group
P031 [Motor NP Volts]
Related Parameter(s):
,
Stop drive before changing this parameter.
Set to the motor nameplate rated volts.
Values
Default:
Based on Drive Rating
Min/Max:
20/Drive Rated Volts
Display:
1 VAC
P032 [Motor NP Hertz]
Related Parameter(s):
,
Stop drive before changing this parameter.
Set to the motor nameplate rated frequency.
Values
Default:
60 Hz
Min/Max:
15/320 Hz
Display:
1 Hz
P033 [Motor OL Current]
Related Parameter(s):
,
,
Set to the maximum allowable motor current.
The drive will fault on an F7
if the value of this parameter is exceeded by 150% for 60
seconds.
Values
Default:
Drive Rated Amps
Min/Max:
0.0/(Drive Rated Amps
×
2)
Display:
0.1 Amps
P034 [Minimum Freq]
Related Parameter(s):
,
,
,
Sets the lowest frequency the drive will output continuously.
Values
Default:
0.0 Hz
Min/Max:
0.0/320.0 Hz
Display:
0.1 Hz
P035 [Maximum Freq]
Related Parameter(s):
,
,
,
Stop drive before changing this parameter.
Sets the highest frequency the drive will output.
Values
Default:
60.0 Hz
Min/Max:
0.0/320.0 Hz
Display:
0.1 Hz