Params defaulted, Analog input loss – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 138

4-4
Troubleshooting
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
No.
Fault
Ty
p
e
(1
)
Description
Action
F15
Load Loss
➀
Output current has dropped
below the level set in
[Load Loss Level].
Check for load loss (i.e., a broken belt).
F17
Input Phase
Loss (FRN 6.xx
and later)
➁
Excessive DC bus ripple
voltage detected. See
[DC Bus Ripple V].
Check incoming power for a missing
phase or blown fuse. If drive is used
intentionally with single phase input,
apply output derating to 35% actual
drive rating.
F29
Analog Input
Loss
➀
An analog input is configured
to fault on signal loss. A signal
loss has occurred.
Configure with
[Analog In
Loss].
1. Check parameters.
2. Check for broken/loose
connections at inputs.
F32
Fan Fdbck Loss
(FRN 6.xx and
later)
➁
A loss of cooling fan feedback
has been detected. (Frames E
and F only)
Make sure cooling fans are clear of
debris and spinning freely. Replace fan
if necessary.
F33
Auto Rstrt Tries
➁
Drive unsuccessfully
attempted to reset a fault and
resume running for the
programmed number of
[Auto Rstrt Tries].
Correct the cause of the fault and
manually clear.
F38
Phase U to Gnd
➁
A phase to ground fault has
been detected between the
drive and motor in this phase.
1. Check the wiring between the drive
and motor.
2. Check motor for grounded phase.
3. Replace drive if fault cannot be
cleared.
F39
Phase V to Gnd
F40
Phase W to Gnd
F41
Phase UV Short
➁
Excessive current has been
detected between these two
output terminals.
1. Check the motor and drive output
terminal wiring for a shorted
condition.
2. Replace drive if fault cannot be
cleared.
F42
Phase UW Short
F43
Phase VW Short
F48
Params
Defaulted
The drive was commanded to
write default values to
EEPROM.
1. Clear the fault or cycle power to the
drive.
2. Program the drive parameters as
needed.
F63
SW OverCurrent
➀
Programmed
Current Trip] has been
exceeded.
Check load requirements and
[SW Current Trip] setting.
F64
Drive Overload
➁
Drive rating of 110% for 1
minute or 150% for 3 seconds
has been exceeded.
Reduce load or extend Accel Time.
F70
Power Unit
➁
Failure has been detected in
the drive power section.
1. Cycle power.
2. Replace drive if fault cannot be
cleared.
F71
Net Loss
The communication network
has faulted.
1. Cycle power.
2. Check communications cabling.
3. Check network adapter setting.
4. Check external network status.
(1)
See