Network points, Metasys n2 f-3 – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 199

Metasys N2
F-3
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Network Points
Table F.7 Binary Inputs
Network Point
Name
Description
ON (“1”)
OFF (“0”)
Type
(NPT)
Address
(NPA)
BI
1
Ready
Logic Status bit 00
Ready
Not Ready
BI
2
Active
Logic Status bit 01
Active
Not Active
BI
3
Cmd Dir
Logic Status bit 02
Forward
Reverse
BI
4
Act Dir
Logic Status bit 03
Forward
Reverse
BI
5
Accel
Logic Status bit 04
Accelerating
Not Accelerating
BI
6
Decel
Logic Status bit 05
Decelerating
Not Decelerating
BI
7
Alarm
Logic Status bit 06
Alarm
No Alarm
BI
8
Fault
Logic Status bit 07
Fault
No Fault
BI
9
At Speed
Logic Status bit 08
At Reference
Not at Reference
BI
10
Main Freq
Logic Status bit 09
Comm Controlled
Not Comm Controlled
BI
11
Oper Cmd
Logic Status bit 10
Comm Controlled
Not Comm Controlled
BI
12
Param Lock
Logic Status bit 11
Locked
Not Locked
BI
13
Digital In 1
Logic Status bit 12
(Drive Terminal #2)
On
Off
BI
14
Digital In 2
Logic Status bit 13
(Drive Terminal #3)
On
Off
BI
15
Digital In 3
Logic Status bit 14
(Drive Terminal #4)
On
Off
BI
16
Digital In 4
Logic Status bit 15
(Drive Terminal #5)
On
Off
BI
17
Digital In 5
Drive Terminal #6
On
Off
BI
18
Digital In 6
Drive Terminal #7
On
Off
BI
19
Digital In 7
Drive Terminal #8
On
Off
Table F.8 Analog Inputs
Network Point
Name
Description
Units
Min/Max
Type
(NPT)
Address
(NPA)
AI
1
Feedback
Feedback
%
0/100
AI
2
Speed
d323 [Output RPM]
RPM
0/24000
AI
3
Current
b003 [Output Current]
A
0.00/Rated
×
2
AI
4
DC Bus Volts
b005 [DC Bus Voltage]
V
0/820
AI
5
Last Fault
b307 [Fault 1 Code]
1
1/100
AI
6
2nd Fault
b308 [Fault 2 Code]
1
1/100
AI
7
Analog In 1
Drive Analog Input #1 (Drive Terminal #13)
%
–
AI
8
Analog In 2
Drive Analog Input #2 (Drive Terminal #17)
%
–
AI
9
Read Value
Read value of Param. selected by AO 10
Varies by the parameter
selected.
AI
10
User In 1
User-defined Input 1
(Param. selected via ADI 1)
AI
11
User In 2
User-defined Input 2
(Param. selected via ADI 2)
AI
12
User In 3
User-defined Input 3
(Param. selected via ADI 3)
AI
13
User In 4
User-defined Input 4
(Param. selected via ADI 4)