D307, D310, D308 – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 120: D309, Advanced display group (continued)

3-62
Programming and Parameters
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Advanced Display Group (continued)
d307 [Fault 1 Code]
Related Parameter(s):
A code that represents a drive fault. The codes will appear in these parameters in the order they occur
(
[Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once.
Refer to
for fault code descriptions.
Values
Default:
Read Only
Min/Max:
0/122
Display:
1
d308 [Fault 2 Code]
Related Parameter(s):
A code that represents the second most recent drive fault. The codes will appear in these parameters
in the order they occur (
[Fault 1 Code] = the most recent fault). Repetitive faults will only be
recorded once. As faults occur, this parameter will be overwritten by [Fault 1 Code]. The value of this
parameter is then moved to [Fault 3 Code].
Refer to
for fault code descriptions.
Values
Default:
Read Only
Min/Max:
0/122
Display:
1
d309 [Fault 3 Code]
Related Parameter(s):
A code that represents the third most recent drive fault. The codes will appear in these parameters in
the order they occur (
[Fault 1 Code] = the most recent fault). Repetitive faults will only be
recorded once. As faults occur, this parameter will be overwritten by [Fault 2 Code].
Refer to
for fault code descriptions.
Values
Default:
Read Only
Min/Max:
0/122
Display:
1
d310 [Fault 1 Time-hr]
Related Parameter(s):
,
Displays the value of the
[Elapsed Time-hr] parameter when the fault occurred.
Values
Default:
Read Only
Min/Max:
0/32767 Hr
Display:
1 Hr
d311 [Fault 1 Time-min]
Related Parameter(s):
,
Displays the value of the
[Elapsed Time-min] parameter when the fault occurred.
Values
Default:
Read Only
Min/Max:
0.0/60.0 Min
Display:
0.1 Min