T082 [Analog Out1 Sel]
Related Parameter(s):
,
,
Sets the analog output signal mode (0-20 mA, 4-20 mA, or 0-10V). The output is used to provide a
signal that is proportional to several drive conditions. This parameter must match DIP Switch AO1
setting.
Setting
Output
Range
Min. Output
Value
Max. Output Value =
[Analog Output Hi]
Filter
(1)
DIP Switch
AO1
Setting
Related
Parameter
0
OutFreq 0-10 0-10V
0V = 0 Hz
[Maximum Freq]
None
10V
1
OutCurr 0-10 0-10V
0V = 0 Amps
200% Drive Rated FLA
Filter A
10V
2
OutTorq 0-10 0-10V
0V = 0 Amps
200% Drive Rated FLA
Filter A
10V
3
OutVolt 0-10
0-10V
0V = 0 Volts
120% Drive Rated Output V None
10V
4
OutPowr 0-10 0-10V
0V = 0 kW
200% Drive Rated Power
Filter A
10V
5
Setpnt 0-10
0-10V
0V = 0.0%
100.0% Setting
None
10V
6
TstData 0-10
0-10V
0V = 0000
65535 (Hex FFFF)
None
10V
7
OutFreq 0-20 0-20 mA 0 mA = 0 Hz
[Maximum Freq]
None
20 mA
8
OutCurr 0-20 0-20 mA 0 mA = 0 Amps
200% Drive Rated FLA
Filter A
20 mA
9
OutTorq 0-20 0-20 mA 0 mA = 0 Amps
200% Drive Rated FLA
Filter A
20 mA
10 OutVolt 0-20
0-20 mA 0 mA = 0 Volts
120% Drive Rated Output V None
20 mA
11 OutPowr 0-20 0-20 mA 0 mA = 0 kW
200% Drive Rated Power
Filter A
20 mA
12 Setpnt 0-20
0-20 mA 0 mA = 0.0%
100.0% Setting
None
20 mA
13 TstData 0-20
0-20 mA 0 mA = 0000
65535 (Hex FFFF)
None
20 mA
14 OutFreq 4-20 4-20 mA 4 mA = 0 Hz
[Maximum Freq]
None
20 mA
15 OutCurr 4-20 4-20 mA 4 mA = 0 Amps
200% Drive Rated FLA
Filter A
20 mA
16 OutTorq 4-20 4-20 mA 4 mA = 0 Amps
200% Drive Rated FLA
Filter A
20 mA
17 OutVolt 4-20
4-20 mA 4 mA = 0 Volts
120% Drive Rated Output V None
20 mA
18 OutPowr 4-20 4-20 mA 4 mA = 0 kW
200% Drive Rated Power
Filter A
20 mA
19 Setpnt 4-20
4-20 mA 4 mA = 0.0%
100.0% Setting
None
20 mA
20 TstData 4-20
4-20 mA 4 mA = 0000
65535 (Hex FFFF)
None
20 mA
21 MinFreq 0-10 0-10V
0V = Min. Freq
[Maximum Freq]
None
10V
22 MinFreq 0-20 0-20 mA 0 mA = Min. Freq
[Maximum Freq]
None
20 mA
23 MinFreq 4-20 4-20 mA 4 mA = Min. Freq
[Maximum Freq]
None
20 mA
24 AnlgIn1 0-10
0-10V
0V = 0.0%
100.0% Setting
Filter A
10V
25 AnlgIn1 0-20
0-20 mA 0 mA = 0.0%
100.0% Setting
Filter A
20 mA
26 AnlgIn1 4-20
4-20 mA 4 mA = 0.0%
100.0% Setting
Filter A
20 mA
27 AnlgIn2 0-10
0-10V
0V = 0.0%
100.0% Setting
Filter A
10V
28 AnlgIn2 0-20
0-20 mA 0 mA = 0.0%
100.0% Setting
Filter A
20 mA
29 AnlgIn2 4-20
4-20 mA 4 mA = 0.0%
100.0% Setting
Filter A
20 mA
(1)
For settings with the filter enabled, if a 0-100% step change occurs, the output will reach 95% in
500 milliseconds, 99% in 810 milliseconds and 100% in 910 milliseconds.
Values
Default:
0
Min/Max:
0/29
Display:
1