Specifications, A-2 supplemental drive information – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 144

A-2
Supplemental Drive Information
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Specifications
Drive Ratings
Catalog
Number
Output Ratings
Input Ratings
Branch Circuit Protection
kW (HP)
Amps
Voltage
Range
kVA Amps Fuses
140M Motor
Protectors
(1)
(2)
Contactors
Min.
Enclosure
Volume
(3)
(in.
3
)
45°C 50°C
200 - 240V AC – 3-Phase Input, 0 - 230V 3-Phase Output
22C-B012N103
2.2 (3.0)
12
12
180-265 6.5
15.5
20
140M-F8E-C16
100-C23
5098
22C-B017N103
3.7 (5.0)
17.5
17.5
180-265 8.8
21
30
140M-F8E-C25
100-C37
5098
22C-B024N103
5.5 (7.5)
24
24
180-265 10.9 26.1
35
140M-F8E-C32
100-C37
5098
22C-B033N103
7.5 (10)
33
33
180-265 14.4 34.6
45
140M-F8E-C45
100-C45
5098
22C-B049A103
11 (15)
49
49
180-265 21.3 51
70
–
100-C60
–
22C-B065A103
15 (20)
65
65
180-265 28.3 68
90
–
100-C85
–
22C-B075A103
18.5 (25)
75
75
180-265 32.5 78
100
–
100-D95
–
22C-B090A103
22 (30)
90
81
180-265 38.3 92
125
–
100-D110
–
22C-B120A103
30 (40)
120
120
180-265 51.6 124
175
–
100-D180
–
22C-B145A103
37 (50)
145
130
180-265 62.4 150
200
–
100-D180
–
380 - 480V AC – 3-Phase Input, 0 - 460V 3-Phase Output
22C-D6P0N103 2.2 (3.0)
6
6
340-528 6.3
7.5
10
140M-D8E-C10
100-C09
5098
22C-D010N103
4.0 (5.0)
10.5
10.5
340-528 10.9 13
20
140M-D8E-C16
100-C16
5098
22C-D012N103
5.5 (7.5)
12
12
340-528 11.9 14.2
20
140M-D8E-C16
100-C23
5098
22C-D017N103
7.5 (10)
17
17
340-528 15.3 18.4
25
140M-D8E-C20
100-C23
5098
22C-D022N103
11 (15)
22
22
340-528 19.2 23
30
140M-F8E-C32
100-C30
5098
22C-D030N103
15 (20)
30
27
340-528 25.8 31
40
140M-F8E-C32
100-C37
5098
22C-D038A103
18.5 (25)
38
38
340-528 33.3 40
50
140M-F8E-C45
100-C60
9086
22C-D045A103
22 (30)
45.5
45.5
340-528 39.1 47
60
–
100-C60
–
22C-D060A103
30 (40)
60
54
340-528 53.3 64
80
–
100-C85
–
22C-D072A103
37 (50)
72
72
340-528 60.7 73
100
–
100-C85
–
22C-D088A103
45 (60)
88
88
340-528 74.9 90
125
–
100-D110
–
22C-D105A103
55 (75)
105
105
340-528 89
107
150
–
100-D140
–
22C-D142A103
75 (100)
142
128
340-528 124.8 150
200
–
100-D180
–
22C-D170A103
90 (125)
170
170
340-528 142
170
250
–
100-D250
–
22C-D208A103
110 (150) 208
208
340-528 167
200
250
–
100-D250
–
22C-D260A103
132 (200) 260
260
340-528 196
235
300
–
100-D300
–
22C-D310A103
160 (250) 310
290
340-528 242
290
400
–
100-D420
–
22C-D370A103
200 (300) 370
370
340-528 304
365
500
–
100-D420
–
22C-D460A103
250 (350) 460
410
340-528 387
465
600
–
100-D630
–
(1)
The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See
.
(2)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240
Wye or Delta, 480Y/277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner
ground, or high-resistance ground systems.
(3)
When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be
installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this
column. Application specific thermal considerations may require a larger enclosure.