F-4 metasys n2 – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 200

F-4
Metasys N2
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Table F.9 Binary Outputs
Network Point
Name
Description
Values
Type
(NPT)
Address
(NPA)
ON (“1”)
OFF (“0”)
BO
1
Run Enable
Logic Command bit 00
Enable
Stop (Coast)
BO
2
Start/Stop
Logic Command bit 00 & 01
Start
Stop (Normal)
BO
3
Jog
Logic Command bit 02
Jog
Not Jog
BO
4
Clear Faults
Logic Command bit 03
Clear Flts
Not Clear Flts
BO
5
Fwd/Rev
Logic Command bit 04 & 05
Forward
Reverse
BO
6
Not Used
Logic Command bit 06
–
–
BO
7
MOP Inc
Logic Command bit 07
Increment
Not Increment
BO
8
Accel 1
Logic Command bit 08
Accel Rate 1
Not Accel 1
BO
9
Accel 2
Logic Command bit 09
Accel Rate 2
Not Accel 2
BO
10
Decel 1
Logic Command bit 10
Decel Rate 1
Not Decel 1
BO
11
Decel 2
Logic Command bit 11
Decel Rate 2
Not Decel 2
BO
12
Ref Sel 1
Logic Command bit 12
BO
BO
13
Ref Sel 2
Logic Command bit 13
14
13
12
BO
14
Ref Sel 3
Logic Command bit 14
0
0
0
= No Command
0
0
1
= P038
[Speed
Reference]
0
1
0
= A142 [Internal Freq]
0
1
1
= Comm - Address 8193
(1)
1
0
0
= A143 [Preset Freq 0]
1
0
1
= A144 [Preset Freq 1]
1
1
0
= A145 [Preset Freq 2]
1
1
1
= A146 [Preset Freq 3]
BO
15
MOP Dec
Logic Command bit 15
Decrement
Not Decrement
BO
16
Pnl Lock
Lock-out Drive Front Panel
Lock
Unlock
BO
17
Digital Out 1
Relay #1 on Drive
(Drive Terminal R1, R2, R3)
On
Off
BO
18
Digital Out 2
Relay #2 on Drive
(Drive Terminal R4, R5, R6)
On
Off
BO
19
Opto Out
Terminal #19
On
Off
(1)
See Writing (06) Reference on
Table F.10 Analog Outputs
Network Point
Name
Description
Units
Min/Max
Type
(NPT)
Address
(NPA)
AO
1
Reference
Reference
%
0/100
AO
2
Accel 1
P039 [Accel Time 1]
Secs
0.0/600.0
AO
3
Decel 1
P040 [Decel Time 1]
Secs
0.0/600.0
AO
4
Mtr OL Current P033 [Motor OL Current]
A
0.0/Rated
×
2
AO
5
PID Setpoint
A157 [PID Setpoint]
%
0/100
AO
6
Analog Out 1
Drive Analog Output #1 (T084)
%
–
AO
7
Analog Out 2
Drive Analog output #2 (T087)
%
–
AO
8
Write Param #
Param. number to write in AO 9
–
0 to Max Param.
AO
9
Write Value
Write value of param. selected by AO 8
Based on AO 8 selected param.
AO
10
Read Param #
Param. number to read in AI 9
–
0 to Max Param.
AO
11
User Out 1
User-defined Output 1
(Param. selected via ADI 5)
Varies by the parameter
selected.
AO
12
User Out 2
User-defined Output 2
(Param. selected via ADI 6)
AO
13
User Out 3
User-defined Output 3
(Param. selected via ADI 7)
AO
14
User Out 4
User-defined Output 4
(Param. selected via ADI 8)