Page 120: The l_lcb_logiccontrolbasic library
The L_LCB_LogicControlBasic library
L_LCB_ActuatorSpeed
120
Lenze · Commissioning of Lenze drives · 1.3 EN - 06/2014
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13.8
L_LCB_ActuatorSpeed
This FB serves to control Lenze Servo Drives 9400 Highline, Inverter Drives 8400 Stateline/8400
Baseline in the speed control mode.
Communication with the devices is possible via the CAN or EtherCAT bus systems.
For a correct function of the FB, the appropriate device application must be active on the controller.
Appropriate applications are marked with the "_Speed" code.
Further information on the device applications can be found in the following section:
Inputs
Function library:
L_LCB_LogicControlBasic
Runtime software licence:
LPC 1x00
MPC 1x00
MPC 2xx0
MPC 3x00
Note!
The FB only works in combination with the following example project:
with the "Actuator speed" application - Actuator Speed
• To create your own function block interconnections, you must use the following
blocks:
•
•
•
L_LCB_ActuatorSpeed
⎯ LogicAxis
xError ⎯ BOOL
BOOL ⎯ xEnableInternalControl
eError ⎯
BOOL ⎯ xDriveEnable
xInternalControlActive ⎯ BOOL
BOOL ⎯ xDriveSetQsp
xDriveError ⎯ WORD
BOOL ⎯ xResetError
xDriveWarning ⎯ AXIS_REF
BOOL ⎯ xEnableSpeedSetPoint
xDriveReady ⎯ BOOL
BOOL ⎯ xJog1Set
xDriveEnabled ⎯ BOOL
BOOL ⎯ xJog2Set
xDriveQspActive ⎯ BOOL
BOOL ⎯ xInverterDirectionSet
xSpeedEqZero ⎯ BOOL
REAL ⎯ rSpeedSetpoint
xDirectionCCW ⎯ BOOL
xHW_Input[1...4] ⎯ BOOL
rSpeedActual ⎯ REAL
Identifier/data type
Information/possible settings
LogicAxis
Structural data for drive control
xEnableInternalControl
BOOL
TRUE: The internal control of the controller can be activated via the "Internal
Control" button.
xDriveEnable
BOOL
TRUE: Deactivate controller inhibit (inverted)