The L_DCO_DriveCommunication library
Enums
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
L_DCO_SDO_ABORTCODE
_DATA_RANGE
20040
The value range for parameters is too great (only for
write access)
• Abort Code 0x06090030
L_DCO_SDO_ABORTCODE
_DATA_RANGE1
20041
The parameter value is too high
• Abort code 0x06090031
L_DCO_SDO_ABORTCODE
_DATA_RANGE2
20042
The parameter value is too low
• Abort Code 0x06090032
L_DCO_SDO_ABORTCODE_MINMAX
20043
The maximum value is lower than the minimum value
• Abort code 0x06090036
L_DCO_SDO_ABORTCODE
_GENERAL
20044
General fault
• Abort code 0x08000000
L_DCO_SDO_ABORTCODE
_TRANSFER
20045
Error when saving/transmitting the data in the
application
• Abort Code 0x08000020
L_DCO_SDO_ABORTCODE
_TRANSFER1
20046
Error when saving/transmitting the data in the
application (caused by local control)
• Abort code 0x08000021
L_DCO_SDO_ABORTCODE
_TRANSFER2
20047
Error when saving/transmitting the data in the
application (caused by current device state)
• Abort Code 0x08000022
L_DCO_SDO_ABORTCODE
_DICTIONARY
20048
Dynamic object directory generation has failed or no
object directory available
• Abort code 0x08000023
L_DCO_SDO_ABORTCODE
_UNKNOWN
20049
Internal slave error (cause unknown)
L_DCO_TRANSFERTABLE_INVALID
20060
Invalid structure L_DCO_TransferData transferred to FB
L_DCO_TransferDriveParameter
Identifier
Error number
(dec)
Description