ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance

2-184
© 2000, ADC Telecommunications, Inc.

DLP-557

Page 2 of 3

6. Move to the Mon Type Alarms toggle fields. The following selections are possible:

Critical

Allows notification of all Critical alarms as they occur.

Major

Allows notification of all Major and Critical alarms as they occur.

Minor

Allows notification of all Minor, Major, and Critical alarms as they occur.

Event

Allows notification of all alarms and events as they occur.

Reference:

TAP-101

Alarm Troubleshooting

7. Assign the selections by pressing Enter or Return.

8. Repeat Steps 3 through 7 for each HDSL facility in the chassis.

Note:

Pressing CONTROL-C and confirming with Y removes all threshold values and

alarm level information from the database for the group and slot selected.

Stop! You have completed this procedure.

6147-B

HDSL PERFORMANCE MONITORING CONFIGURATION

Group: 6 Circuit: 1 Circuit ID:

15 MINUTE DAILY
=================== ===================
MONTYPE THRESHOLD ALM LEVEL THRESHOLD ALM LEVEL
======= ========= ========= ========= =========
FCP 5 EVENT 480 EVENT
CVP 6893 EVENT 67579 EVENT
ESP 65 EVENT 648 EVENT
SESP 10 EVENT 100 EVENT
SEFSP 10 EVENT 100 EVENT

CVs PER SES: 165

Press CONTROL-A For Assistance, CONTROL-C To Clear All PM Counts

Figure 557-1. HDSL PM Configuration Screen (Typical)