Dlp-530 – ADC Soneplex Broadband System User Manual
Page 121
ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance
2-98
© 2000, ADC Telecommunications, Inc.
DLP-530
Page 3 of 3
Table 530-1. ODS2 Configuration Fields, continued
FIELD
TYPE
OPTIONS
DESCRIPTION
DEFAULT
T2 Service State
Toggle
Leave this field at OOS at this time to avoid undesirable reporting of alarms.
Select IS after completing the remaining configurations.
OOS
BER Alarm
Threshold
Toggle
Set to OFF or set between
10–6 and 10–10
The average Bit Error Ratios of both the
incoming optical signals are monitored by the
ODS2. By monitoring BERs, the ODS2 is
capable of triggering a minor alarm when any of
the monitored signals degrades below the BER
threshold level.
10–8
BER Switch
Threshold
Toggle
Set between 10–4 and 10–
10
This sets the threshold at which the APS will be
executed.
10–6
Provision
Toggle
YES
Brings up T1 default settings and allows
configuration changes.
NO
(set for each T1)
NO
Facility not provisioned.
T1 Service State
Toggle
Leave this field at OOS at this time to avoid undesirable reporting of alarms.
Select IS after completing the remaining configurations.
OOS
Line Code
Toggle
AMI
Alternate Mark Inversion
AMI
(set for each T1)
B8ZS
Bipolar Eight-Zero Substitution
Circuit Identifier
Input
Enter up to 20 characters
or leave blank.
Use alphanumeric characters; embedded
hyphens are allowed.
None
(set for each T1)
Remote Pulse
Equalization
Toggle
0–133 ft., 133–226 ft.,
226–399 ft., 399–533 ft.,
533–655 ft., or NOT
APPL.
The DS1 signal output provides standard DSX
signal levels which can be compensated for at
various distances (i.e., cable length).
0–133 ft.
Remote Frame
Format
Fixed
Locked at NOT APPL.
NOT APPL
Remote PPS (Path
Protection Switch)
Threshold
Fixed
Locked at NOT APPL.
NOT APPL
T2 Service State
Toggle
IS (In-Service)
Places facility in service and allows T2 alarm
reporting by the MPU.
OOS
OOS (Out-Of-Service)
Removes facility from service and stops T2
alarm reporting by the MPU.
T1 Service State (set
for each T1)
Toggle
IS (In-Service)
Places facility in service and allows T1 alarm
reporting by the MPU.
OOS
OOS (Out-Of-Service)
Removes facility from service and stops T1
alarm reporting by the MPU.