ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance

2-110
© 2000, ADC Telecommunications, Inc.

DLP-533

Page 2 of 5

11783-A

RLX CONFIGURATION

Group: 1 Slot: 1 Circuit ID:

Unit Equip State : EQUIPPED Pulse Equalization : NOT APPL
Unit Service State: OOS LBO Setting : UNIT SWITCH
T1 Provision : YES Programmable Loopback : DISABLED
T1 Service State : OOS NID Loopback : ENABLED
Line Code : AMI Loopback Activation Code : 1101001111010011
Framing Format : AUTO Loopback Deactivate Code : 1001001110010011
Network DS1 Source: NRZ Lpbk Timeout Disable Code: 1101010111010110
BER Threshold : 1E-7 Loopback Timeout Period : 0 minutes
Span Power Setting: ENABLED Network Keep Alive : AIS

DS0 Channel 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
(B = blocked) . . . . . . . . . . . . . . . . . . . . . . . .

Unit Switch Settings: Pulse Equalization: NOT APPL Span Power: DISABLED
NID: DISABLED LBO: 7.5 dB

Press CONTROL-A For Assistance

Figure 533-1. RLX Configuration Screen (Broadband Chassis)

Note:

The Unit Service State field default is UNEQUIPPED and the T1 Provision field

default is NO. When the Unit Service State field is set to EQUIPPED and the T1
Provision field is set to YES, this screen shows all other field defaults, as above.

Table 533-1. RLXIOR Configuration Fields

FIELD

TYPE

OPTIONS

DESCRIPTION

DEFAULT*

Group

Toggle

1, 2, 3, 4, 5, 6, or 7
(groups 6 and 7 are not
available in the 19-inch
LEC chassis)

Specifies the module’s group number
designated on the chassis.

1

Slot

Toggle

1, 2, 3, or 4

Specifies the module’s slot number in the
group designated on the chassis.

1

Circuit Identifier

Input

Enter up to 20 characters

This represents the customer’s circuit ID.
The first and last characters must be alpha or
numeric; middle characters can be alpha,
numeric, or hyphens.

Blank

Unit Equip State

Toggle

Equipped

Establishes communication with the MPU.
Module must be set to EQUIPPED before
remaining selections are allowed.

UNEQUIPPED

Unequipped

No communication with the MPU.

*Note: The RLXIOR configuration field default values shown in this manual are valid for a system with an MPU installed.

(continued)