Figure 542-1, Of the alarm, Figure 542-2 – ADC Soneplex Broadband System User Manual
Page 170: T1 hlxc/hrx/hlxr nend, Dlp-542, Page 2 of 4, Figure 542-1. active alarms screen (sample)
ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance
2-147
© 2000, ADC Telecommunications, Inc.
DLP-542
Page 2 of 4
6675-A
ACTIVE ALARMS
Legend:
Access ID=Identifier[-]Shelf-Grp-Slot[-Site(1=Lcl,2=Rmt) | -Loop(1=Lp 1,2=Lp 2)]
Access ID Locn Circuit ID Condition Status ACO
---------------- ---- -------------------- ---------------- ------ ---
T2-1-3-1 NEND OPTICAL LOS MJ NO
T2-1-3-1 NEND OPTICAL LOF MJ NO
HDSL-1-7-1-1 NEND RECOVERY MN NO
HDSL-1-7-1-1 NEND LOF MJ NO
HDSL-1-7-1-1 NEND T-BERP MN NO
HDSL-1-7-1-1 NEND T-SNR EV NO
HDSL-1-7-1-1 FEND LOF MJ NO
HDSL-1-7-1-1 FEND T-BERP MN NO
HDSL-1-7-1-1 FEND T-SNR EV NO
HDSL-1-7-1-2 NEND RECOVERY MN NO
HDSL-1-7-1-2 NEND LOF MJ NO
HDSL-1-7-1-2 NEND T-BERP MN NO
HDSL-1-7-1-2 NEND T-SNR EV NO
HDSL-1-7-1-2 FEND LOF MJ NO
HDSL-1-7-1-2 FEND T-BERP MN NO
HDSL-1-7-1-2 FEND T-SNR EV NO
Page 1 of 1 Press CONTROL-A for assistance
Figure 542-1. Active Alarms Screen (Sample)
KEY
NEND means "PM information collected directly from incoming T1 signals, both at local and remote sites."
FEND means "ESF PRM information collected at the opposite ends of spans from the affected circuit and
returned to the system via the ESF Datalink, both at local and remote sites". The framing format must be
ESF in order for FEND information to be displayed.
Note: For Site 1, FEND information is at A; for Site 2, FEND information is at B.
10263-A
NEND
NEND
FEND
HRX
HLXC
HLXR
FEND
REMOTE
(SITE = -2)
LOCAL
(SITE = -1)
LOOP 1
LOOP 2
LOOP 1
LOOP 2
DS1
DS1
DS1
DS1
TO NETWORK
TO CUSTOMER
A
B
Figure 542-2. T1 HLXC/HRX/HLXR NEND and FEND Locations