Table 125. cr3000 settings – Campbell Scientific CR3000 Micrologger User Manual
Page 542

Appendix B. Status Table and Settings
542
Table 125. CR3000 Settings
Settings are accessed through the Campbell Scientific Device Configuration Utility (DevConfig) via direct-serial and IP connections, or through
PakBusGraph via most CR3000 supported telecommunications options.
Setting Description
Default
Entry
OS Version
Specifies the version of the operating system currently in the CR3000.
Serial Number
Specifies the CR3000 serial number assigned by the factory when the CR3000 was
calibrated.
Station Name
Specifies a name assigned to this station.
PakBus Address
This setting specifies the PakBus® address for this device. The value for this setting
must be chosen such that the address of the device is unique in the scope of the
datalogger network. Duplication of PakBus® addresses in two or more devices can lead
to failures and unpredictable behavior in the PakBus® network. The following values
are the default addresses of various types of software and devices and should probably
be avoided:
Device
PB Address
LoggerNet
4094
PC400
4093
PC200
4092
Visual Weather 4091
RTDAQ
4090
DevConfig 4089
NL100
678
All other devices 1
1
Security Level 1
Specifies Level 1 Security. Zero disables all security. Range: 0 to 65535. See Security
(p. 70).
0
Security Level 2
Specifies Level 2 Security. Zero disables levels 2 & 3. Range: 0 to 65535. See Security
(p. 70).
0
Security Level 3
Specifies Level 3 Security. Zero disables level 3. Range: 0 to 65535. See Security
(p.
0
UTC Offset
The offset, in seconds, that the CR3000's local time is from UTC. This offset is used in
email and HTML headers, since these protocols require the time stamp to be reflected in
UTC. This offset will also be used by the GPS instruction, NetworkTimeProtocol
instruction, and DaylightSavingTime functions when enabled.
-1 (Disabled)
Is Router
This setting controls whether the CR3000 is configured as a router or as a leaf node. If
the value of this setting is non-zero, the CR3000 is configured to act as a PakBus
®
router. That is, it is able to forward PakBus
®
packets from one port to another. To
perform its routing duties, a CR3000 configured as a router will maintain its own list of
neighbors and send this list to other routers in the PakBus
®
network. It will also obtain
and receive neighbor lists from other routers.
If the value of this setting is zero, the CR3000 is configured to act as a leaf node. In this
configuration, the CR3000 will not be able to forward packets from one port to another
and it will not maintain a list of neighbors. Under this configuration, the CR3000 can
still communicate with other dataloggers and wireless sensors. It cannot, however, be
used as a means of reaching those other dataloggers.
0
PakBus Nodes Allocation
Specifies the amount of memory that the CR3000 allocates for maintaining PakBus
®
routing information. This value represents roughly the maximum number of PakBus
®
nodes that the CR3000 is able to track in its routing tables.
50