A.2.3.2 multiple-source – Campbell Scientific CR3000 Micrologger User Manual
Page 480

Appendix A. CRBasic Programming Instructions
480
Moment 
Stores the mathematical moment of a value over the output interval. 
Syntax
Moment(Reps, Source, Order, DataType, DisableVar)
PeakValley 
Detects maxima and minima in a signal. 
Syntax
PeakValley(DestPV, DestChange, Reps, Source, Hysteresis)
Sample 
Stores the current value at the time of output. 
Syntax
Sample(Reps, Source, DataType)
SampleFieldCal 
Writes field calibration data to a table.  See Calibration Functions
(p. 525).
 
SampleMaxMin 
Samples a variable when another variable reaches its maximum or minimum for 
the defined output period. 
Syntax
SampleMaxMin(Reps, Source, DataType, DisableVar)
StdDev 
Calculates the standard deviation over the output interval. 
Syntax
StdDev(Reps, Source, DataType, DisableVar)
Totalize 
Sums the total over the output interval. 
Syntax
Totalize(Reps, Source, DataType, DisableVar)
A.2.3.2 Multiple-Source
ETsz 
Stores evapotranspiration (ETsz) and solar radiation (RSo). 
Syntax
ETsz(Temp, RH, uZ, Rs, Longitude, Latitude, Altitude, Zw, Sz,
DataType, DisableVar)
RainFlowSample 
Stores a sample of the CDM_VW300RainFlow into a data table. 
Syntax
RainFlowSampe(Source, DataType)