Campbell Scientific CR3000 Micrologger User Manual
Page 531

Appendix B. Status Table and Settings
531
Table 124. Status-Table Fields and Descriptions
Fieldname Description
Variable
Type
Default
Range
Edit?
Info
Type
RevBoard
xxx.yyy 
xxx = hardware revision 
number; yyy = clock chip 
software revision; stored in 
FLASH memory. 
Integer
Status
StationName1
Sets a name internal to the 
CR3000. Stored in flash 
memory. Not to be confused 
with the station name set in 
datalogger support software. 
See foot note for limitations. 
String
Yes
Config
PakBusAddress2
CR3000 PakBus address.
String
1
1 to 3999
Yes
Config PB
ProgName
Name of current (running) 
program. 
String
Status
StartTime
Time the program began 
running. 
Time
Status
RunSignature
Signature of the compiled 
binary data structure for the 
current program. Value is 
independent of comments 
added or non-functional 
changes to the program. 
Often changes with 
operating-system changes. 
Integer
Status
ProgSignature
Signature of the current 
running program file 
including comments. Does 
not change with operating 
system changes. 
Integer
Status
Battery
Current value of the battery 
voltage. Measurement is 
made in the background 
calibration. 
Float
9.6-16
Vdc
Measure
PanelTemp
Current wiring-panel 
temperature. Measurement is 
made in the background 
calibration. 
Float
Measure
WatchdogErrors3
Number of Watchdog errors 
that have occurred while 
running this program. 
Integer 0
0
Yes 
Reset by 
changing to 0 
Error
LithiumBattery4
Current voltage of the 
lithium battery. Measurement 
is updated in background 
calibration. 
Float
2.7-3.6
Vdc
Measure