2 low-level ac (p1 - p4), 3 switch closure (p1 - p4), 2 pulse input on digital i/o channels c1 - c8 – Campbell Scientific CR3000 Micrologger User Manual
Page 321: 1 high frequency mode

Section 8. Operation
321
8.1.5.1.2 Low-Level ac (P1 - P4)
Rotating magnetic-pickup sensors commonly generate ac output voltages ranging 
from thousandths of Volts at low rotational speeds to several volts at high 
rotational speeds. Pulse channels contain internal signal-conditioning hardware 
for measuring low-level ac-output sensors. When configured for low-level ac, P1 
through P4 measure signals ranging from 20-mV RMS (
±28 mV peak) to 14-V
RMS (
±20 V peak). Internal ac coupling is incorporated in the low-level ac
hardware to eliminate dc offset voltages of up to
±0.5 Vdc.
8.1.5.1.3 Switch Closure (P1 - P4)
Switch-closure mode measures switch closure events, such as occur with a 
common tipping bucket rain gage. An internal 100-k
Ω pull-up resistor pulls an
input to 5 Vdc with the switch open, whereas a switch closure to ground pulls the 
input to 0 V. An internal 3.3-ms time-constant RC-debounce filter eliminates 
multiple counts from a single switch closure event. 
8.1.5.2 Pulse Input on Digital I/O Channels C1 - C8
Digital I/O channels C1 – C8 can be used to measure pulse inputs between -8.0 
and +16 Vdc. Low frequency mode (<1 kHz) allows for edge timing and 
measurement of period and frequency. High-frequency mode (up to 400 kHz) 
allows for edge counting only. Switch-closure mode enables measurement of dry-
contact switch closures up to 150 Hz. Digital I/O channels can be programmed 
with either PulseCount() or TimerIO() instructions. 
When configured for input, signals connected to C1 – C8 are each directed into a 
digital-CMOS input buffer that recognizes inputs ≥ 3.8 V as being high and inputs 
≤ 1.2 V as being low. 
Low-level ac signals cannot be measured directly by digital I/O channels. Refer 
to the appendix Pulse / Frequency Input-Expansion Modules
(p. 562)
for information
on peripheral modules available to convert low-level ac signals to square-wave 
signals. 
Read More! Review digital I/O channel specifications in CR3000 Specifications
.
Caution Contact Campbell Scientific for signal conditioning information if a 
pulse input < -8.0 or > +16 Vdc is to be measured. Under no circumstances 
should voltages greater than 
±50 V be connected to channels C1 – C8.
8.1.5.2.1 High Frequency Mode
Digital I/O channels have a small 25-ns input RC-filter time constant between the 
terminal block and the CMOS input buffer, which allows for higher-frequency 
pulse counting (up to 400 kHz) when compared with pulse-input channels P1 – 
P4 (250 kHz maximum). 
Switch-closure mode is a special case edge-count function. Because of signal 
conditioning for debounce, 150 Hz is the maximum input frequency at which 
switch closures can be measured on digital I/O channels. 
