Page 82

background image

NORDAC SK 750E Manual

82

Subject to technical amendments

BU 0750 GB-3311

7.3 Basic parameters

Parameter

Setting value / Description / Note

Parameter
set

Available in Option

P100

Parameter set

Always visible

0 ... 3
[ 0 ]

Selection of the parameters sets to be parameterised. 4 parameter sets are available. All parameter
set-dependent parameters are identified by P.

The selection of the operating parameter set is performed via a digital input or the Bus control.
Switching can take place during operation (online).

Setting

Digital input
function [8]

Digital input
function [17]

ControlBox
display

0 =

Parameter set 1

LOW

LOW

1

2

1 =

Parameter set 2

HIGH

LOW

2

1

2 =

Parameter set 3

LOW

HIGH

1

2

3 =

Parameter set 4

HIGH

HIGH

2

1

If enabled via the keyboard (ControlBox, PotentiometerBox or ParameterBox), the operating
parameter set will match the settings in P100.

P101

Copy parameter set

Always visible

0 ... 4
[ 0 ]

After confirmation with the ENTER key, a copy of the parameter set selected in P100 >Parameter
set< is written to the parameter set dependent on the value selected here

0 =

Do not copy

1 =

Copies the active parameter set to parameter set 1

2 =

Copies the active parameter set to parameter set 2

3 =

Copies the active parameter set to parameter set 3

4 =

Copies the active parameter set to parameter set 4

P102

Start-up time

P

Always visible

0 ... 320.00 s
[ 2.00 ]
or [ 3.00 ]

The start-up time is the time corresponding to the linear frequency rise from 0Hz to the set maximum
frequency (P105). If an actual setpoint of <100% is being used, the acceleration time is reduced
linearly according to the setpoint which is set.
The start-up time can be extended by certain circumstances, e.g. FI overload, setpoint lag, rounding
or if the current limit is reached.

P103

Braking time

P

Always visible

0 ... 320.00 s
[ 2.00 ]
or [ 3.00 ]

The braking time is the time corresponding to the linear frequency reduction from the set maximum
frequency to 0Hz (P105). If an actual setpoint <100% is being used, the braking time reduces
accordingly.

The braking time can be extended by certain circumstances, e.g. by the selected >Switch-off mode<
(P108) or >Ramp smoothing< (P106).