P1101, P1201, P1202 – NORD Drivesystems BU0750 User Manual
Page 68: P1203, P1204, P1205
NORDAC SK 750E Manual
68
Subject to technical amendments
BU 0750 GB-3311
Menu group < Parameterisation> (P11xx)
Parameter
Setting value / Description / Note
P1101
Object selection
Selection of the object to be parameterised.
The ongoing parameterisation process relates to the object selected. Only the devices and storage
objects detected during the bus scan are displayed in the selection list.
Note:
This parameter is not shown if only one device is recognised and there is no
storage object in the ParameterBox.
Value range: I1 - I5 and S1 - S5
Menu group < Parameter Management > (P12xx)
Parameter
Setting value / Description / Note
P1201
Copy - Source
Selection of the actual source object to be copied.
In the selection list, only the frequency inverters and storage media detected during the bus scan
are shown.
Value range: I1 - I5 and S1 - S5
P1202
Copy - Target
Selection of actual target object to copy.
In the selection list, only the frequency inverters and storage media detected during the bus scan
are shown.
Value range: I1 - I5 and S1 - S5
P1203
Copy - Start
This parameter triggers a transfer process, whereby all the parameter data sets selected in >Copy
– Source< are transferred to the object specified in the >Copy – Target< parameter.
While data is being overwritten, an information window appears with acknowledgement. The
transfer starts after acknowledgement.
P1204
Load default values
With this parameter, the parameter data sets of the object selected are described with factory
settings.
This function is particularly important for editing storage objects. It is only via this parameter that a
hypothetical frequency inverter can be loaded and edited with the ParameterBox.
Value range: I1 - I5 and S1 - S5
P1205
Delete memory
With this parameter the data in the selected storage medium is deleted.
Value range: S1 - S5