NORD Drivesystems BU0750 User Manual
Page 116
NORDAC SK 750E Manual
116
Subject to technical amendments
BU 0750 GB-3311
Parameter
Setting value / Description / Note
Parameter
set
Available with option
P543
Actual bus value 1
P
Always visible
0 ... 12
[ 1 ]
The return value 1 can be selected for bus actuation in this parameter.
Note: Further details can be found in the respective BUS instruction manuals.
0 = Off
1 = Actual frequency
2 = Actual speed
3 = Current
4 = Torque current (100% = P112)
5 = Status of digital inputs and outputs
2
6 = Actual position (only with PosiCon, SK 700E)
7 = Actual position (only with PosiCon, SK 750E)
8 = Setpoint frequency
9 = Error number
10 = Actual position increment
3
(only with PosiCon, SK 750E)
11 = Setpoint position increment
3
(only with PosiCon, SK 750E)
12 =
Bus I/O Out Bits 0 … 7
P544
Actual bus value 2
P
Always visible
0 ... 12
[ 0 ]
In this parameter zhe return value 2 can be selected for bus control.
Note: Further details can be found in the respective BUS instruction manuals.
This parameter is identical to P543.
P545
Actual bus value 3
P
Always visible
0 ... 12
[ 0 ]
In this parameter zhe return value 3 can be selected for bus control. This is only available if
P546
3.
Note: Further details can be found in the respective BUS instruction manuals.
This parameter is identical to P543.
3
Assignment of the digital inputs in P543/ 544/ 545 = 5 for SK 750E
Bit 0 = DigIn 1
Bit 1 = DigIn 2
Bit 2 = DigIn 3
Bit 3 = DigIn 4
Bit 4 = DigIn 5
Bit 5 = DigIn 6
Bit 6 = DigIn 7 (POS or ENC)
Bit 7 = DigIn 8
Bit 8 = DigIn 9 (POS)
Bit 9 = DigIn 9 (POS)
Bit 10 = DigIn 10 (POS)
Bit 11 = DigIn 12 (POS)
Bit 12 = Rel 1
Bit 13 = Rel 2
Bit 14 = Rel 3 (POS)
Bit 15 = Rel 4 (POS)
2
The setpoint/actual position corresponding to an 8192 increment encoder.