beautypg.com

10 parameter overview, user settings – NORD Drivesystems BU0750 User Manual

Page 126

background image

NORDAC SK 750E Manual

126

Subject to technical amendments

BU 0750 GB-3311

7.10 Parameter overview, User settings

(P)

Parameter set-dependent, these parameters can be differently adjusted in 4 parameter sets.

Parameter

No.

Name

Factory

setting

Setting after commissioning

P 1

P 2

P 3

P 4

OPERATING DISPLAYS (7.2)

P000

Operating display

P001

Selection display

0

P002

Factor display

1.00

BASIC PARAMETERS (7.3)

P100

Parameter set

0

P101

Copy parameter set

0

P102

(P) Start-up time [s]

2.0 or 3.0

P103

(P) Braking time [s]

2.0 or 3.0

P104

(P) Minimum frequency [Hz]

0.0

P105

(P) Maximum frequency [Hz]

50.0

P106

(P) Ramp rounding [%]

0

P107

(P) Brake reaction time [s]

0.00

P108

(P) Disconnection mode

1

P109

(P) DC brake current [%]

100

P110

(P) DC braking time on

2.0

P111

(P) P factor torque limit [%]

100

P112

(P) Torque current limit [%]

401 (OFF)

P113

(P) Jog frequency [Hz]

0.0

P114

(P) Brake reaction time [s]

0.00

MOTOR DATA / CHARACTERISTIC CURVE PARAMETERS (7.4)

P200

(P) Motor list

0

P201

(P) Nominal motor frequency [Hz]

50.0 *

P202

(P) Nominal speed [rpm]

1460 *

P203

(P) Nominal motor current [A]

21.5 *

P204

(P) Nominal motor voltage [V]

400 *

P205

(P) Nominal power [kW]

11.00 *

P206

(P) Motor cos phi

0.84 *

P207

(P) Motor circuit [star=0/delta=1]

1 *

P208

(P) Stator resistance [

]

1.08*

P209

(P) No load current [A]

11.6 *

P210

(P) Static boost [%]

100

P211

(P) Dynamic boost [%]

100

P212

(P) Slip compensation [%]

100

P213

(P) Amplification ISD control [%]

100

P214

(P) Torque precontrol [%]

0

P215

(P) Boost precontrol [%]

0

P216

(P) Boost time precontrol [s]

0.0

*) dependent on inverter power or P200