NORD Drivesystems BU0750 User Manual
Page 122
NORDAC SK 750E Manual
122
Subject to technical amendments
BU 0750 GB-3311
Parameter
Setting value / Description / Note
Parameter
set
Available with option
P715
Enablement time
Always visible
0.0 ... 9999 h
This parameter shows the time for which the FI was enabled and supplied current to the output.
P716
Actual frequency
Always visible
-400.0 ... 400.0 Hz
Displays the actual output frequency.
P717
Actual rotation speed
Always visible
-9999...9999 rpm
Displays the actual motor speed calculated by the FI.
P718
... - 01
... - 02
... - 03
Actual setpoint frequency
Always visible
-400.0 ... 400.0 Hz
Displays the frequency specified by the setpoint. (see also 10.1 Setpoint processing)
... - 01 = Actual setpoint frequency from the setpoint source
... - 02 = Actual setpoint frequency after processing in the FI status machine
... - 03 = Actual setpoint frequency after frequency ramp
P719
Actual current
Always visible
0.0 ... 500.0 A
Displays the actual output current.
P720
Actual torque current
Always visible
-500.0 ... 500.0 A
Displays the actual calculated torque-developing output current. The basis for calculation are
the motor data P201 ... P209.
-500.0 ... 500.0 A
negative values = generator, positive values = motor.
P721
Actual field current
Always visible
-500.0 ... 500.0 A
Displays the actual calculated field current. The basis for calculation are the motor data P201 ...
P209.
P722
Actual voltage
Always visible
0 ... 500 V
Displays the actual AC voltage supplied by the FI output.
P723
Actual voltage component U
d
Always visible
-500 ... 500 V
Displays the actual field voltage component.
P724
Actual voltage component U
q
Always visible
-500 ... 500 V
Displays the actual torque voltage component.
P725
Actual cos
Always visible
0.00 ... 1.00
Displays the actual calculated power factor of the drive.
P726
Apparent power
Always visible
0.00 ... 300.00 kVA
Displays the actual calculated apparent power. The basis for calculation are the motor data
P201 ... P209.
P727
Effective power
Always visible
0.00... 300.00 kW
Displays the actual calculated effective power. The basis for calculation are the motor data
P201 …P209.
P728
Mains voltage
Always visible
0 ... 1000 V
Displays the actual mains voltage at the FI input.
P729
Torque
Always visible
-400 ... 400 %
Displays the actual calculated torque. The basis for calculation are the motor data P201 ...
P209.