NORD Drivesystems BU0750 User Manual
Page 104
NORDAC SK 750E Manual
104
Subject to technical amendments
BU 0750 GB-3311
Parameter
Setting value / Description / Note
Parameter set Available with option
P426
Emergency stop time
P
Always visible
0 ...100.00 s
[ 0.1 ]
or [ 1.0 ]
Braking time setting for the emergency stop function, which can be triggered by digital input, bus
control, keyboard or automatically in the case of an error.
The emergency stop time is the time for the linear frequency decrease from the set maximum
frequency (P105) to 0Hz. If an actual setpoint <100% is being used, the emergency stop time is
reduced correspondingly.
P427
Emergency stop on error
Always visible
0 ... 3
[ 0 ]
Activation of automatic emergency stop following error
0 = OFF: Automatic emergency stop following error is deactivated
1 = Mains supply failure: Automatic emergency stop following mains supply failure
2 = Error: Automatic emergency stop following fault
3 = Mains supply failure and error: Automatic emergency stop following mains supply failure
and error
P428
Automatic start
P
Always visible
0 ... 1
[ 0 ]
In the standard setting (P428 = 0
Off) the inverter requires a flank to enable (signal change from
"Low
High") at the relevant digital input.
In the setting On
1, the FI reacts to a High level. This function is only possible if the FI is controlled
using the digital inputs. (see P509).
In some cases, the FI must start up directly when the mains are switched on. For this P428 = 1
On
can be set. If the enable signal is permanently switched on, or equipped with a cable jumper, the FI
starts up immediately.