7.9 Information
BU 0750 GB-3311
Subject to technical amendments
123
Parameter
Setting value / Description / Note
Parameter
set
Available with option
P730
Field
Always visible
0 ... 100 %
Displays the actual field in the motor calculated by the inverter. The basis for calculation are the
motor data P201 ... P209.
P731
Actual parameter set
Always visible
0 ... 3
Displays the actual parameter set.
0 = Parameter set 1
1 = Parameter set 2
2 = Parameter set 3
3 = Parameter set 4
P732
U phase current
Always visible
0.0 ... 500.0 A
Displays the actual U phase current.
Note: This value can, due to the measurement procedure used even with symmetrical output
currents, deviate somewhat from the value in P719.
P733
V phase current
Always visible
0.0 ... 500.0 A
Displays the actual V phase current.
Note: This value can, due to the measurement procedure used even with symmetrical output
currents, deviate somewhat from the value in P719.
P734
W phase current
Always visible
0.0 ... 500.0 A
Displays the actual W phase current.
Note:
This value can, due to the measurement procedure used even with symmetrical
output currents, deviate somewhat from the value in P719.
P735
Encoder speed
ENC
POS
-9999 ... +9999 rpm
Displays the actual speed supplied by the encoder.
P736
DC link current
Always visible
0 ... 1000 V DC
Displays the actual link voltage.
P740
... - 01
...
... - 06
Process data bus In
Always visible
0 ... FFFF hex
This parameter informs about the actual control
word and the setpoints that are transferred via the
bus systems.
... - 01 = Control word
... - 02 = Setpoint 1 (P546)
... - 03 = Setpoint 1 High byte
... - 04 = Setpoint 2 (P547)
... - 05 = Setpoint 3 (P548)
... - 06 = Bus-In-Bit (P546-P548)
P741
... - 01
...
... - 06
Process data Bus Out
Always visible
0 ... FFFF hex
This parameter provides information about the
actual status word and the actual values that are
transferred via the bus systems.
... - 01 = Status word
... - 02 = Actual value 1 (P543)
... - 03 = Actual value 1 High byte
... - 04 = Actual value 2 (P544)
... - 05 = Actual value 3 (P545)
... - 06 = Bus-Out-Bit (P543-P545)
P742
Database version
Always visible
0 ... 9999
Displays the internal database version of the FI.
P743
Inverter type
Always visible
0.00 ... 250.00
Displays the inverter power in kW, e.g.15
“
FI with 15 kW nominal power.