7.9 Information

BU 0750 GB-3311

Subject to technical amendments

123

Parameter

Setting value / Description / Note

Parameter
set

Available with option

P730

Field

Always visible

0 ... 100 %

Displays the actual field in the motor calculated by the inverter. The basis for calculation are the
motor data P201 ... P209.

P731

Actual parameter set

Always visible

0 ... 3

Displays the actual parameter set.

0 = Parameter set 1
1 = Parameter set 2

2 = Parameter set 3
3 = Parameter set 4

P732

U phase current

Always visible

0.0 ... 500.0 A

Displays the actual U phase current.

Note: This value can, due to the measurement procedure used even with symmetrical output
currents, deviate somewhat from the value in P719.

P733

V phase current

Always visible

0.0 ... 500.0 A

Displays the actual V phase current.

Note: This value can, due to the measurement procedure used even with symmetrical output
currents, deviate somewhat from the value in P719.

P734

W phase current

Always visible

0.0 ... 500.0 A

Displays the actual W phase current.

Note:

This value can, due to the measurement procedure used even with symmetrical
output currents, deviate somewhat from the value in P719.

P735

Encoder speed

ENC

POS

-9999 ... +9999 rpm

Displays the actual speed supplied by the encoder.

P736

DC link current

Always visible

0 ... 1000 V DC

Displays the actual link voltage.

P740

... - 01

...

... - 06

Process data bus In

Always visible

0 ... FFFF hex

This parameter informs about the actual control
word and the setpoints that are transferred via the
bus systems.

... - 01 = Control word

... - 02 = Setpoint 1 (P546)

... - 03 = Setpoint 1 High byte

... - 04 = Setpoint 2 (P547)

... - 05 = Setpoint 3 (P548)

... - 06 = Bus-In-Bit (P546-P548)

P741

... - 01

...

... - 06

Process data Bus Out

Always visible

0 ... FFFF hex

This parameter provides information about the
actual status word and the actual values that are
transferred via the bus systems.

... - 01 = Status word

... - 02 = Actual value 1 (P543)

... - 03 = Actual value 1 High byte

... - 04 = Actual value 2 (P544)

... - 05 = Actual value 3 (P545)

... - 06 = Bus-Out-Bit (P543-P545)

P742

Database version

Always visible

0 ... 9999

Displays the internal database version of the FI.

P743

Inverter type

Always visible

0.00 ... 250.00

Displays the inverter power in kW, e.g.15

FI with 15 kW nominal power.