NORD Drivesystems BU0750 User Manual
Page 134
NORDAC SK 750E Manual
134
Subject to technical amendments
BU 0750 GB-3311
Display
Fault
Cause
Remedy
Group
Details in
P700 / P701
E003
3.0
Inverter overcurrent
I
2
t limit has triggered e.g.. > 1.5 x I
n
for 60s (see
also P504)
Continuous overload at inverter output
3.1
Overcurrent, chopper
I
2
t limit for braking resistance has triggered
(please also note P555, P556, P557)
Avoid overcurrent in brake resistance
3.2
Overcurrent derating
Monitoring 125%
Derating (power reduction) at f < 2 Hz
125% overcurrent for 50ms
for fan drives: enable flying start (P520)
E004
4.0
Overcurrent module
Error signal from module (short duration)
Short circuit or earthing at FI output
Use external output choke (motor cable is
too long)
E005
5.0
Link circuit overvoltage
DC link voltage is too high
Reduce energy return by means of a braking
resistance
Extend braking time (P103)
If necessary, set switch-off mode (P108) with
delay (not for lifting equipment)
Extend emergency stop time (P426)
5.1
Mains overvoltage
Mains voltage is too high
Please check (380V-20% ... 480V+10%), or
200/240V
10%
E006
6.0
Link circuit undervoltage
(Charging error)
Inverter mains/link voltage too low
Check mains voltage (380V-20% ...
480V+10%), or 200/240V
10%
6.1
Mains undervoltage
E007
7.0
Mains phase error
One of the three mains input phases was or is
interrupted.
Check mains phases (380V-20% ...
480V+10%), or 200/240V
10%
All three mains phases must be symmetrical.
OFF
Note:
OFF appears in the display when the three mains phases are uniformly
reduced, i.e. when a normal mains switch off occurs during operation.