9 Technical data
BU 0750 GB-3311
Subject to technical amendments
139
9 Technical data
9.1 General Data
Function
Specification
Output frequency
0.0 ... 400.0Hz
Pulse frequency
3.0 ... 16.0kHz (Standard = 6kHz)
Typical overload capacity
150% for 60s, peak value 200% for 3.5s
Protective measures against
Overtemperature
of
the
frequency
inverter
Over and under-voltage
Short-circuit, earth fault
Overload, idle running
Regulation and control
Sensorless current vector control (ISD)
Field-orientated control
Linear V/f characteristic curve
Setpoint input analog / PID input
(optional)
0 ... 10V,
10V, 0/4 ... 20mA
Analog setpoint resolution
10 bit based on measurement range
Analog output
0 ... 10V scaleable (optional)
Setpoint consistency
analog < 1%
digital < 0.02% (optional)
Motor temperature monitoring
I
2
t-motor (UL/CUL certified), PTC / Bimetal switch (optional, not UL/CUL)
Ramp times
0 ... 320s
Control outputs (optional)
1 or 2 relays 28V DC / 230V AC, 2A
Interface (optional)
According to option:
RS 485 (standard)
CANbus
CANopen
DeviceNet
Profibus DP
InterBus
AS interface
Efficiency of frequency inverter
approx. 95%
Ambient temperature
0°C ... +50°C (S1 mode), 0°C ... +60°C (S3 mode) without condensation
Storage and transport temperature
-25°C ... +60/70°C
Long-term storage
See Section 10.6.1
Protection class
IP54 air cooled version / IP65 water cooled version
Electrical isolation
Control terminals (digital and analog inputs)
Max. installation altitude above sea level
Up to 1000m:
No power reduction
1000...4000m:
1%/ 100m power reduction (up to 2000m overvoltage
cat. 3)
2000...4000m:
Only overvoltage category 2 is complied with, external
overvoltage protection at the mains input is necessary
Waiting time between two mains switching
cycles
60 sec for all devices in normal operating cycle
Ambient conditions
Transport (IEC 60721-3-2):
Vibration: 2M2
Operation (IEC 60721-3-3):
Vibration: 3M7;
Climate: 3K3
Certifications
CE, UL, cUL