NORD Drivesystems BU0750 User Manual
Page 110
NORDAC SK 750E Manual
110
Subject to technical amendments
BU 0750 GB-3311
Parameter
Setting value / Description / Note
Parameter
set
Available with option
P505
Absolute minimum frequency
P
Always visible
0.0 ... 10.0 Hz
[ 2.0 ]
States the frequency value that cannot be undershot by the FI. If the setpoint becomes smaller than
the absolute minimum frequency, the FI switches off or changes to 0.0Hz.
At the absolute minimum frequency, braking control (P434 or P441) and the setpoint delay (P107)
are actuated. If a setting value of "Zero" is selected, the brake relay does not switch during
reversing.
When controlling lifting equipment, this value should be set at a minimum of 2Hz. From 2Hz and
higher, the current control of the FI operates and a connected motor can supply sufficient torque.
P506
Automatic error acknowledgement
Always visible
0 ... 7
[ 0 ]
In addition to the manual error acknowledgement, an automatic one can also be selected.
0 =
No automatic error acknowledgement.
1 ... 5 = Numberof permissible automatic malfunction acknowledgments within one mains-on
cycle. After mains off and switch on again, the full number is available again.
6 =
Always, an error message will always be acknowledged automatically if the cause of the
error is no longer present.
7 =
ENTER key, acknowledgement is only possible using the ENTER key or by mains switch-
off. No acknowledgement is implemented by removing the enable!
P507
PPO type
Always visible
1 ... 4
[ 1 ]
Only with the technology unit Profibus, DeviceNet or InterBus
See also additional descriptions BU 0020, BU 0080, BU 0070
P508
Profibus address
Always visible
1 ... 126
[ 1 ]
Profibus address, only with the Profibus technology unit
See also the additional description for the Profibus control