4.6 ParameterBox error messages
BU 0750 GB-3311
Subject to technical amendments
71
Display
Fault
Cause
Remedy
222
Inverter extension level not
recognised
An unknown module has been detected in the frequency inverter
(Customer interface).
Please check the components installed in the
frequency inverter
If necessary, check the software version of the
ParameterBox and the frequency inverter.
223
Bus configuration has
changed
After restoring the last Bus configuration, a device is reported that is
different from the one stored.
This error can only occur if the parameter >Auto Bus Scan< is set to
OFF and another device has been connected to the ParameterBox.
Activate the Automatic Bus Scan function.
224
Device is not supported
The frequency inverter type connected to the ParameterBox is not
supported!
The ParameterBox cannot be used with this frequency
inverter.
225
The connection to the
inverter is blocked
Access to a device that is not ONLINE (previously Time Out error).
Carry out a bus scan via the parameter >Bus Scan<
(P1001).
ParameterBox operating error
226
Source and target are
different devices
Copying objects of different types (from / to different inverters) is not
possible.
227
Source is empty
Copying of data from a deleted (empty) storage medium
228
This combination is not
permitted
Target and source for the copying function are the same. The
command cannot be carried out.
229
Object selected is empty
Parameterisation attempt of a deleted storage medium
230
Different software versions
Warning
Copying objects with different software versions can lead to problems
when transferring parameters.
231
Invalid password
Attempt to alter a parameter without a valid Box password being
entered in parameter >Box password< P 1306.
232
Bus scon only during
operation: ONLINE
A bus scan (search for a connected frequency inverter) is only possible
when in ONLINE mode.