Display
Fault
Cause
Remedy
Group
Details in
P700 / P701
E010
10.0
Telegram downtime
(P513)
Data transfer is faulty. Check P513.
Check external Bus connection.
Check bus protocol program process.
Check Bus Master.
Check 24V supply of internal CAN/CANopen
Bus.
Nodeguarding error (internal CANopen)
Bus Off error (internal CAN Bus)
10.2
External bus module telegram
timeout
Telegram transfer is faulty.
Check external connection.
Check bus protocol program process.
Check Bus Master.
10.4
External bus module initialisation
failure
Check P746.
Bus module not correctly plugged in.
Check Bus module current supply.
10.1
External Bus module system
failure
Further details can be found in the respective
additional BUS operating instructions.
10.3
10.5
10.6
10.7
10.8
External module communication
error
Connection fault / error in the external
component
E011
11.0
Reference voltage (SK CU1-...)
Reference voltage of customer unit faulty
(10V / 15V). Only displayed if control is via the
control terminals (P509 = 0/1).
Check control terminals connection for short-
circuit.
I/O module may not be correctly engaged.
E012
12.0
Customer Watchdog
The Watchdog function is selected at a digital
input and the impulse at the corresponding digital
input is not present for longer than the time set in
parameter P460 >Watchdog time<.