9 information – NORD Drivesystems BU0750 User Manual
Page 120
NORDAC SK 750E Manual
120
Subject to technical amendments
BU 0750 GB-3311
7.9 Information
Parameter
Setting value / Description / Note
Parameter
set
Available with option
P700
Actual error
Always visible
0.0 ... 20.9
Actual error present. Further details in Section 8
Error messages
.
ControlBox:
Descriptions of the individual error numbers can be found under Error
Messages.
ParameterBox: Errors are displayed in plain text, further information can be found under Error
Messages.
P701
.. - 01
...
.. - 05
Last fault 1...5
Always visible
0.0 ... 20.9
This parameter stores the last 5 faults. Further details in Section 8
Error messages
.
The ControlBox must be used to select the corresponding memory location 1-5 (Array), and
confirmed using the ENTER key to read the stored error code.
P702
.. - 01
...
.. - 05
Freq. previous fault 1...5
Always visible
-400.0 ... 400.0 Hz
This parameter stores the output frequency that was being delivered at the time the fault
occurred. The values of the last 5 errors are stored.
The ControlBox must be used to select the corresponding memory location 1-5 (Array), and
confirmed using the ENTER key to read the stored error code.
P703
.. - 01
...
.. - 05
Current, previous fault 1...5
Always visible
0.0 ... 500.0 A
This parameter stores the output current that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
The ControlBox must be used to select the corresponding memory location 1-5 (Array), and
confirmed using the ENTER key to read the stored error code.
P704
.. - 01
...
.. - 05
Voltage, previous fault 1...5
Always visible
0 ... 500 V AC
This parameter stores the output voltage that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
The ControlBox must be used to select the corresponding memory location 1-5 (Array), and
confirmed using the ENTER key to read the stored error code.
P705
.. - 01
...
.. - 05
UZW, previous fault 1...5
Always visible
0 ... 1000 V DC
This parameter stores the link voltage that was being delivered at the time the error occurred.
The values of the last 5 errors are stored.
The ControlBox must be used to select the corresponding memory location 1-5 (Array), and
confirmed using the ENTER key to read the stored error code.