Display
Fault
Cause
Remedy
Group
Details in
P700 / P701
E013
13.0
Encoder error
Encoder error (only for special extension unit
Encoder/PosiCon)
5V Sense signal not present at encoder input
13.1
Speed slip error
The slip speed error limit was reached.
Increase setting in P327.
13.2
Slip error switch-off monitoring
The slip error monitoring was triggered; the motor
could not follow the setpoint.
Increase setting value for torque limit in P112.
E014
14.0
Slave check
PosiCon
– Error 1
Further details can be found in the description
BU 0710
14.1
Host check
14.2
Reference point travel error
14.3
Absolute encoder voltage
monitoring bit
14.4
Incremental encoder error
14.5
Position change and speed do not
match
14.6
Slip error between absolute and
incremental encoders
14.7
Maximum position exceeded
14.8
Minimum position undershot
E015
15.0
Incorrect software version
PosiCon
– Error 2
Further details can be found in the description
BU 0710
15.1
Watchdog PosiCon
15.2
Stack overflow PosiCon
15.3
Stack underflow PosiCon
15.4
Undefined opcode PosiCon
15.5
Protected instruction PosiCon
15.6
Illegal word access PosiCon
15.7
Illegal instruction access PosiCon
15.8
EPROM error PosiCon
E016
16.0
Motor phase error
A motor phase is not connected.
Check P539
Check motor connection
16.1
Motor current monitoring for
braking mode
Required exciting current not achieved at moment
of switch-on.
Check P539
Check motor connection