App index – Yokogawa Standalone MW100 User Manual
Page 93
2-43
IM MW100-17E
Response
1
2
3
App
App
Index
Data Block Member Values
Member Name
Value
Year
00 to 99 (70 to 99: 1970 to 1999, 00 to 69: 2000 to 2069)
Month
1 to 12
Day
1 to 31
Hours
0 to 23
Minute
0 to 59
Second
0 to 59
Milliseconds
0 to 990
Computation start
0, 1
Message information
Bits 0:0, 1
Bits 1:0, 1
•
•
Setting key
0x0000 to 0xffff
Channel number
1 to 60:
Measurement Channel
101 to 400:
MATH channels
Alarm Status
0:
No specification
1:
Upper limit alarm setting
2:
Lower limit alarm setting
3:
Differential upper limit alarm setting
4:
Differential lower limit alarm setting
5:
Upper limit on rate-of-change alarm setting
6:
Lower limit on rate-of-change alarm setting
7:
Delay upper limit alarm setting
8:
Delay lower limit alarm setting
Data value
–32767 to 65535
–9999999 to 99999999
Unused
Undefined
Special Data Values
During special statuses, measured and computed values are as shown in the table
below.
Special Data Value Type
Value
+OVER
0x7fff 0x7fff
–OVER
0x8001 0x8001
Error
0x8004 0x8004
Note
• Added information and alarm statuses are output without regard to the byte order specified
in the BO command.
• Messages inside added information is uncertain.
2.3 Binary Output